-57-
• Confirm that the vertical louver is normally geared with the shaft of Stepping Motor.
• If the regular torque is detected when rotating the vertical louver with hands
⇒
Normal
• Check the connecting condition of CN-U/D Connector
• Check the soldering condition(on PCB) of CN-U/D Connector
Check the operating circuit of the vertical louver
• Confirm that there is DC +12V between pin
➀
of CN-U/D and GND.
• Confirm that there is a soldering short at following terminals.
- Between
41
,
42
,
43
and
44
of MICOM
- Between
4
,
5 , 6
and
7
of IC01M
- Between
10
,
11 , 12
and
13
of IC01M
When the horizontal louver does not operate.
Trouble 5
If there are no problems after above checks.
• Confirm the assembly condition that are catching and interfering parts in the link of the
vertical louver