- 28 -

Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes

LGE Internal Use Only

3. Connecting The Cable Between Indoor Unit and Outdoor Unit

1) Connect the cable to the Indoor unit.

• 

Connect the cable to the indoor unit by connecting the wires to the terminals on the control board in
dividually according to the outdoor unit connection.

(Ensure that the color of the wires of the outdoor  unit and

the terminal No. are the same as those of the indoor unit.)

The earth wire should be longer than the common wires.

Air 

Conditioner

Main power source

If a power plug is not to be used, provide a circuit breaker
between power source and the unit as shown below.

Circuit Breaker

Use a circuit
breaker or time
delay fuse.

CAUTION

CAUTION

The power cord connected to the "A" unit should be
complied with the following specifications
(Type "B" approved by HAR or SAA).

7k~14k

18k

24k~28k

30k, 32k

36k, 38k

1.0

1.5

2.5

2.5

5.5

Unit(A)

Indoor

Indoor

Indoor

Outdoor

Outdoor

Cable Type(B)

H05VV-F

H05VV-F H05VV-F H05RN-F H05RN-F

NORMAL CROSS

-SECTIONAL AREA

Grade

7k~14k

18k

24k~28k

1.0

1.5

2.5

Cable Type(B) H07RN-F H07RN-F H07RN-F

NORMAL

CROSS

-SECTIONAL

AREA

Grade

30k, 32k

36k, 38k

0.75

0.75

Cable Type(B) H07RN-F H07RN-F

NORMAL CROSS

-SECTIONAL AREA

Grade

(mm

2

)

(mm

2

)

(mm

2

)

The power connecting cable connected to the indoor
and outdoor unit should be complied with the following
specifications
(Type "B" approved by HAR or SAA).

NORMAL
CROSS-SECTIONAL
AREA 0.75mm

2

 

• The above circuit diagram is subject to change with-

out notice. 

• Be sure to connect wires according to the wiring dia-

gram.

• Connect the wires firmly, so that not to be pulled out

easily.

• Connect the wires according to color codes by refer-

ring the wiring diagram.

CAUTION

• When installing, refer to the circuit diagram on the

Control Box of Indoor Unit.

• When installing, refer to the wiring diagram on the

Control Cover Inside Outdoor Unit.

Содержание LS-C082QMA0

Страница 1: ...S T246AAG AAL ACL ACG AAM LS T246CAG BAG ADG ADL LDL LS T266CAG FAG AAL CDL LS T1865AG LS T212CAG LS T1860AL LS C186TGD0 TLB0 TGM0 TLA0 LS C266TGD0 TLB0 TGM0 TLA0 TGF0 CAUTION Before Servicing the unit read the safety precautions in General SVC manual Only for authorized service personnel Internal Use Only http biz lgservice com ...

Страница 2: ...isplay Function 20 Self diagnosis Function 20 Installation 21 Operation 32 Disassembly of the parts Indoor Unit 34 2 way 3 way Valve 37 Cycle Troubleshooting Guide 44 Electronic Parts Troubleshooting Guide 45 Electronic Control Device 52 Schematic Diagram 56 Exploded View 58 2 Copyright 2009 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only ...

Страница 3: ... Brand G 2nd LG Brand N 2nd OEM Brand Basic A 0 Plasma Filter B 1 Auto Swing Plasma Filter C 2 Telephone LED Display D 3 Telephone LCD Display E 4 Auto Swing Plasma Filter Telephone LCD F 5 Low Ambient Ambient change G 6 Plasma Filter Low Ambient Ambient change H 7 Internet J 8 Auto Swing Plasma Filter Oxygen Generator K 9 Auto Swing Soft Start L Z Auto Swing Star Rating M Y Auto Swing Star Rating...

Страница 4: ...0Hz 3Phase 5 200 220V 50Hz D 440 460 60Hz 3Phase 6 220 240V 50Hz E 265V 60Hz 7 110V 50 60Hz F 200V 50 60Hz 8 380 415V 50Hz 9 380 415V 60Hz 7 Chassis A Z Name of Chassis of Unit Ex LSP SP Chassis 8 Look A Z Look Color Artcool Model 9 Function A Z 10 Serial No 1 9 LG Model De ARTCOOL COLOR velopment Serial No Basic A Basic 4Way B Plasma Filter C Plasma Filter 4 Way D Tele LCD E Tele LCD Nano plasma ...

Страница 5: ... unit will be stopped after 1 2 3 4 5 6 7 hours The fan is switched to intermittent or irregular operation The fan speed is automatically switched from high to low speed The louver can be set at the desired position or swing up and down automatically Indoor Unit Operation ON OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Control Time Delay Safety Co...

Страница 6: ...rol Cooling model only Heating model only TEMPERATURE LOW HIGH Cooling Operation Mode Heating Operation Mode Auto Operation Mode Fan Operation Mode Horizontal Airflow Direction Control Button Optional Room Temperature Display Setting the Time or Timer PLASMA Optional ON OFF SET PLASMA CANCEL Fan Speed Selection Low Med High CHAOS High 39 C Low 11 C OFF ON OFF ON Cancel Sleep Mode Timer ON or Timer...

Страница 7: ...Control Cooling model only Heating model only TEMPERATURE LOW HIGH Cooling Operation Mode Heating Operation Mode Auto Operation Mode Air Circulation Horizontal Airflow Direction Control Button Optional Room Temperature Checking Setting the Time or Timer PLASMA Optional Fan Speed Selection Low Med High ON OFF CANCEL SET 2nd F High 39 C Low 11 C OFF ON OFF ON Cancel Sleep Mode Timer ON or Timer OFF ...

Страница 8: ...4 6 35 1 4 6 35 3 8 9 52 3 8 9 52 1 4 6 35 1 4 6 35 1 2 12 7 1 2 12 7 5 8 15 88 5 8 15 88 1 2 12 7 1 2 12 7 O O O O O O O O O O O O 1 5mm2 x 0 7mm2 1 5mm2 2 5mm2 x 0 7mm2 2 5mm2 x 0 7mm2 2 5mm2 x 0 7mm2 1 5mm2 x 0 7mm2 1 5mm2 1 5mm2 2 5mm2 2 5mm2 2 5mm2 1 5mm2 Air Circulation Noise Level Input m3 min dB A 3 Indoor Outdoor Indoor Outdoor Indoor Outdoor Indoor Outdoor Indoor Outdoor Liquid Gas Servi...

Страница 9: ...ght 2009 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only Installation plate D H W MODEL DIM Unit W mm 1090 H mm 314 D mm 172 ALL MODELS Dimensions 1 Indoor Unit ...

Страница 10: ...and service purposes LGE Internal Use Only W L7 L6 L8 L9 D L1 L2 L3 L10 L11 L4 L5 H Gas side Liquid side 2 Outdoor Unit MODEL DIM W mm 870 H mm 655 D mm 320 L1 mm 370 L2 mm 340 L3 mm 25 L4 mm 630 L5 mm 25 L6 mm 546 L7 mm 162 L8 mm 162 L9 mm 54 L10 mm 74 5 L11 mm 79 ALL MODELS ...

Страница 11: ... INDOOR UNIT OUTDOOR UNIT HEAT EXCHANGE EVAPORATOR HEAT EXCHANGE EVAPORATOR HEAT EXCHANGE CONDENSER HEAT EXCHANGE CONDENSER COMPRESSOR COMPRESSOR ACCUMU LATOR GAS SIDE GAS SIDE VALVE LIQUID SIDE LIQUID SIDE VALVE CAPILLARY TUBE CAPILLARY TUBE CHECK VALVE Heating Model only COOLING HEATING REVERSING VALVE Heating Model Only 1 Cooling Only Models 2 Cooling Heating Models ...

Страница 12: ... CAPACITOR 1 L 2 N POWER BR BK Plained GN YL BR BL GN YL BL WH Ribbed 1 L 2 N MOTOR CN MOTOR CN TAB1 CN AC DC CN AC DC CN TH THERMISTOR STEP MOTOR STEP MOTOR H V ASM RD AIR CLEAN PLASMA SAFETY S W1 SAFETY S W2 BK BK BK BK BK CN U D CN L R CN DISP DISPLAY PWB ASM INDOOR WIRING DIAGRAM 3854A20142B SW FORCE T BLOCK TO OUTDOOR UNIT TRIAC AC PWB ASM DC PWB ASM OR BK BR 4 RY COMP FUSE 250V T2A 3 YL SH C...

Страница 13: ...eep timer cancel or appliance operation pause Timer Indicator ON while in timer mode on off OFF when timer mode is completed or canceled Defrost Indicator OFF except when hot start during heating mode operation or while in defrost control Cooling Mode Operation When the intake air temperature reaches 0 5 C below the setting temp the compressor and the outdoor fan stop When it reaches 0 5 C above t...

Страница 14: ...0 min heating mode operation at 4 min interval whether to carry out defrost control or not and the time of defrost control are determined according to the following conditions 1 While in heating mode operation the maximum of the indoor pipe temperature is measured and it is com pared with the present indoor pipe temperature to get the difference of the indoor pipe temperatures the maximum temperat...

Страница 15: ... outdoor fan and the 4 way valve are off and only the indoor fan is operated for 15 seconds Then an operation mode is selected according to the intake air temp at that moment as follows 24 C Inatake Air Temp Fuzzy Operation for Cooling 21 C Inatake Air Temp 24 C Fuzzy Operation for Dehumidification Inatake Air Temp 21 C Fuzzy Operation for Heating If any of the operation modes among cooling dehumi...

Страница 16: ... for Heating According to the setting temperature selected by Fuzzy rule when the intake air temp is 3 C or more above the setting temp the compressor is turned off When below the setting temp the compressor is turned on Compressor ON Temp Setting Temp Compressor OFF Temp Setting Temp 3 C At the beginning of Fuzzy mode operation the setting temperature is automatically selected according to the in...

Страница 17: ...tops While the appliance is on pause the sleep timer mode cannot be input While in cooling mode operation 30 min later since the start of the sleep timer the setting temperature increases by 1 C After another 30 min elapse it increases by 1 C again When the sleep timer mode is input while in cooling cycle mode the airflow speed of the indoor fan is set to the low When the sleep timer mode is input...

Страница 18: ... used The operation will be started if the power button is pressed If you want to stop operation re press the button While in forced operation the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation Test operation During the TEST OPERATION the unit operates in cooling mode at high speed fan regardless of room tem perature and resets in 18 1...

Страница 19: ...are turned off in order to protect the indoor evaporator pipe from frosting When the indoor pipe temp is 7 C or higher after 3 min pause of the compressor the compressor and the outdoor fan is turned on according to the condition of the room temperature Buzzer Sounding Operation When the appliance operation key is input by the remote control the short beep beep sounds When the appliance pause key ...

Страница 20: ...short Indoor Thermistor assembly check SVC check point 1 Heating Model 2 Cooling Model Cooling Soft Dry Fan Heating Cooling Soft Dry Fan Sleep Mode Sleep Mode Timer Mode Timer Mode Hot start Defrost PLASMA Mode PLASMA Mode Telephone Control Mode Telephone Control Mode Operation Indicator Timer Indicator Sleep Timer Indicator Defrost Indicator PLASMA Indicator Telephone control Indicator Telephone ...

Страница 21: ...er weight into account and select a place where noise and vibration are minimum Select a place so that the warm air and noise from the air conditioner do not disturb neighbors 2 Piping length and elevation Installation 1 Installation of indoor Outdoor unit More than A More than B More than 2 3m More than B More than 10cm More than 10cm More than 60cm More than 60cm More than 70cm Install the indoo...

Страница 22: ...n plate routing of the wiring to power outlets is through the walls typi cally Drilling the hole through the wall for piping connections must be done safely 4 Drill a hole in the wall Drill the piping hole with a ø70mm hole core drill Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side Installation Plate Type A screw 5 7mm 3 16 5 16 Indoor WALL ...

Страница 23: ...emove burrs in order to avoid drop ping burrs into the tubing 3 Putting nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal not possible to put them on after flaring work 4 Flaring work Firmly hold copper pipe in a die in the dimension shown in the table above Carry out flaring work using flaring tool as shown below 5 Check Compare ...

Страница 24: ...side the room insulate the hose with an insulation material so that dripping from sweating condensation will not damage furniture or floors Foamed polyethylene or equivalent is recommended 4 Indoor unit installation Hook the indoor unit onto the upper portion of the installation plate Engage the two hooks of the rear top of the indoor unit with the upper edge of the instal lation plate Ensure that...

Страница 25: ...ther by wrap ping them with vinyl tape for enough to cover where they fit into the rear piping housing section 1 Route the indoor tubing and the drain hose to the required piping hole position 2 Insert the piping drain hose and the connecting cable into the piping hole For left rear piping mm inch kg m Ø6 35 1 4 1 8 Ø9 52 3 8 4 2 Ø12 7 1 2 5 5 Ø15 88 5 8 6 6 Ø19 05 3 4 6 6 Outside diameter Torque ...

Страница 26: ...en the flare nut by hand Tighten the flare nut with a wrench When extending the drain hose at the indoor unit install the drain pipe 7 Wrap the insulation material around the con necting portion Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material Bind them together with vinyl tape so that there is no gap Wrap the area which accommodates the rear piping hou...

Страница 27: ... right Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound 3 Connection of the pipes Outdoor 1 Align the center of the pipings and sufficiently tighten the flare nut by hand 2 Finally tighten the flare nut with torque wrench until the wrench clicks When tightening the flare nut with torque wrench ensure the directio...

Страница 28: ...cations Type B approved by HAR or SAA 7k 14k 18k 24k 28k 30k 32k 36k 38k 1 0 1 5 2 5 2 5 5 5 Unit A Indoor Indoor Indoor Outdoor Outdoor Cable Type B H05VV F H05VV F H05VV F H05RN F H05RN F NORMAL CROSS SECTIONAL AREA Grade 7k 14k 18k 24k 28k 1 0 1 5 2 5 Cable Type B H07RN F H07RN F H07RN F NORMAL CROSS SECTIONAL AREA Grade 30k 32k 36k 38k 0 75 0 75 Cable Type B H07RN F H07RN F NORMAL CROSS SECTIO...

Страница 29: ...he casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could cause burn out of the wires 3 Specification of power source 4 Confirm that electrical capacity is sufficient 5 See to that the starting voltage is maintained at more than 9...

Страница 30: ...t to connect an additional drain hose the end of the drain outlet should be routed above the ground Secure the drain hose appropriately 2 In cases where the outdoor unit is installed below the indoor unit perform the following Tape the piping drain hose and connecting cable from down to up Secure the tapped piping along the exterior wall using saddle or equivalent 3 In cases where the Outdoor unit...

Страница 31: ...e is more than 8 C 46 F Cool ing or Heating 4 For reference the gas side pressure of optimum con dition is as below Cooling NOTE If the actual pressure is higher than shown the system is most likely over charged and charge should be removed If the actual pressure are lower than shown the system is most likely undercharged and charge should be added The air conditioner is now ready for use Bolt Tub...

Страница 32: ...d in cooling mode CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up down airflow direction ON OFF TIMER BUTTONS Used to set the time of starting and stopping operation TIME SETTING BUTTONS Used to adjust the time TIMER SET CANCEL BUTTONS Used to set the timer when the desired time is obtained and to cancel the Timer operation SLEEP MODE AUTO BUTTON Used to set Sleep M...

Страница 33: ...d stopping operation TIME SETTING BUTTONS Used to adjust the time TIMER SET CANCEL BUTTON Used to set the timer when the desired time is obtained and to cancel the Timer operation SLEEP MODE AUTO BUTTON Used to set Sleep Mode Auto operation AIR CIRCULATION BUTTON Used to circulate the room air without cooling or heating ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature PLASMA OPT...

Страница 34: ...move the Grille from the Chassis Set the up and down air discharge louver to open position horizontally by finger pressure Remove the securing screws To remove the Grille pull the lower left and right side of the grille toward you slightly tilted and lift it straight upward 1 Before removing the control box be sure to take out the wire screwed at the other end Display P C B Conductor Step Motor Co...

Страница 35: ...ws Pull the control box out from the chassis careful ly 3 To remove the Discharge Grille Unhook the discharge grille and pull the dis charge grille out from the chassis carefully 4 To remove the Evaporator Remove 3 screws securing the evaporator at the left 2EA in the Eva Holder at the right 1EA Caution label When repair do not damage the Caution label Caution label ...

Страница 36: ...he tab is clear of the slot 5 To remove the Motor Cover Remove 2 securing screw Pull the motor cover out from the chassis carefully 6 To remove the Cross Flow Fan Loosen the screw securing the cross flow fan to the fan motor do not remove Lift up the right side of the cross flow fan and the fan motor separate the fan motor from the cross flow fan Remove the left end of the cross flow fan from the ...

Страница 37: ...osed Open Open clockwise counter clockwise connected manifold gauge Open Open Open with charging cylinder Open Open Open with charging cylinder Open Open Open Open Works Shipping Air purging Installation Operation Pumping down Transfering Evacuation Servicing Gas charging Servicing Pressure check Servicing Gas releasing Servicing 1 2 3 4 5 6 Valve cap Open position Closed position Pin Service port...

Страница 38: ...remove the cap from the 3 way valve s service port Using the hexagonal wrench to press the valve core pin discharge for three seconds and then wait for one minute Repeat this three times 5 Use torque wrench to tighten the service port nut to a torque of 1 8kg cm 6 Set the 3 way valve to the back seat 7 Mount the valve stem nuts to the 2 way and 3 way valves 8 Check for gas leakage At this time esp...

Страница 39: ... the push pin to the service port 4 Air purging of the charge hose Open the low pressure valve on the charge set slightly to air purge from the charge hose 5 Set the 2 way valve to the closed position 6 Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg cm2 g 7 Immediately set the 3 way valve to the closed position Do this quickly so that the gauge ends up in...

Страница 40: ...purging the air use a torque wrench to tighten the flare nut on the 2 way valve 4 Check for gas leakage Check the flare connections for gas leakage 5 Discharge the refrigerant Close the valve on the gas cylinder and dis charge the refrigerant until the gauge indicates 3 to 5 kg cm2 g 6 Disconnect the charge set and the gas cylin der and set the 2 way and 3 way valves to the open position Be sure t...

Страница 41: ... the service port 3 Open the valve Lo side on the charge set and discharge the refrigerant until the gauge indicates 0 kg cm2 G If there is no air in the refrigerant cycle the pressure when the air conditioner is not run ning is higher than 1 kg cm2 G discharge the refrigerant until the gauge indicates 0 5 to 1 kg cm2 G if this is the case it will not be neces sary to apply a evacuatin Discharge t...

Страница 42: ...t the gauge needle has moved toward 76 cmHg vacuum of 4 mmHg or less 3 Close the valve Lo side on the charge set turn off the vacuum pump and confirm that the gauge needle does not move approxima tely 5 minutes after turning off the vacuum pump 4 Disconnect the charge hose from the vacuum pump Vacuum pump oil If the vacuum pump oil becomes dirty or depleted replenish as needed Lo Open Open Vacuum ...

Страница 43: ... it can be charged with a little at a time approximately 150g each time while operating the air conditioner in the cooling cycle however one time is not suffi cient wait approximately 1 minute and then repeat the procedure pumping down pin 4 Immediately disconnect the charge hose from the 3 way valve s service port Stopping partway will allow the gas to be dis charged If the system has been charge...

Страница 44: ...e difference between intake and discharge air depends on room air humidity When the room air humidity is relativery higher temperature difference is smaller When the room air humidity is relatively lower tem perature difference is larger 2 Check temperature and pressure of refrigeration cycle Notice 1 The suction pressure is usually 4 5 6 0 kg cm2 G Cooling at normal condition 2 The temperature ca...

Страница 45: ...ecting cable Check PWB Assembly Fuse Pattern damage Varistor ZNR01J Check the connection housing for contacting Connector related to CN TAB1 RY COMP NO 3 Connector related to CN MOTOR Connector contacting of Outdoor Fan Compressor Display PWB Assembly Check Check each load Indoor Outdoor Fan Motor Com pressor Stepping Motor and contacting condition of related connector Main PCB Board Operation Che...

Страница 46: ...ntrol When the mark is displayed in LCD screen replace bat tery Check the contact of CN DISP1 connector When the compressor stopped Indoor Fan is driven by a low speed At this point the wind speed is not controlled by the remote controller When operated in the Sleeping Mode the wind speed is set to the low speed by force Check Display PWB Assembly Voltage between CN DISP1 DC 5V Check the connectin...

Страница 47: ...onnector are in bad connection or are not engaged Compressor Outdoor Fan is stopped Check the related circuit of RY FAN Check the indoor temperature sensor is disconnected or not About 10kΩ at 25 C Turn off Main Power Check the electrical wiring diagram of outdoor side Check the abnormal condition for the component of Compressor Out door Fan Motor Check the open or short of conmecting wires betwee...

Страница 48: ...he Fuse AC250V T2A Turn ON Main Power Check the related circuit of indoor Fan Motor The pin NO 63 of Micom and the part for driving TRIAC the input and output signal of IC01M PIN NO 7 10 Check the pattern Check the TRIAC TRIAC Open Indoor Fan Motor never operate TRIAC short Indoor Fan Motor always operates in case of ON or OFF 4 When indoor Fan does not operate The voltage of PIN NO 1 orange and 3...

Страница 49: ...rmal Check the connecting condition of CN U D Connector Check the soldering condition on PWB of CN U D Connector If there are no problems after above checks Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver Check the operating circuit of the Vertical Louver Confirm that there is DC 12V between pin RED of CN U D and GND Confirm tha...

Страница 50: ... RY 4WAY Check the indoor room temperature is disconnected or not about 10KΩ at 25 C Check the indoor pipe temperature is disconnected or not about 5KΩ at 25 C Turn ON Main Power Check the DC voltage on the PWB ASSEMBLY The details of check are as followings Check point Between Micom NO 59 and GND Between IC01M NO 11 and GND Comp ON DC 5V Below DC 1V Comp OFF DC 0V About DC 12V Check point Between...

Страница 51: ...ng and service purposes LGE Internal Use Only Turn off Main Power Check the electrical wiring diagram of outdoor side Check the abnormal condition for the component of Compressor Out door Fan Motor 4 way Check the open or short of connecting wires between indoor and outdoor ...

Страница 52: ... Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only Electronic Control Device 1 MAIN P W B ASSEMBLY AC PART TOP VIEW BOTTOM VIEW 1 MAIN P W B ASM AC COOLING MODEL HEAT PUMP MODEL ...

Страница 53: ... 53 Copyright 2009 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only 2 MAIN P W B ASSEMBLY DC PART TOP VIEW BOTTOM VIEW TOP VIEW BOTTOM VIEW ...

Страница 54: ...009 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only 3 DISPLAY ASSEMBLY 6871A20194 TOP VIEW BOTTOM VIEW BOTTOM VIEW BOTTOM VIEW 6871A30009 TOP VIEW 6871A20227 TOP VIEW ...

Страница 55: ...2009 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only 6871A20391 TOP VIEW BOTTOM VIEW C01A C01A C01A 88SEG 88SEG C01A C01A C01A 88SEG 6871A20476 TOP VIEW BOTTOM VIEW ...

Страница 56: ... 56 Copyright 2009 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only Schematic Diagram Cooling Model LED TYPE ...

Страница 57: ... 57 Copyright 2009 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only HVB TYPE PLASMA ...

Страница 58: ...iew and Replacement Parts List 1 Indoor Unit 346810 35211B 135516 W0CZZA 263232 352150 266090 146811 145200 354210 263230 264110 268711C 131410 149304 359011 342800 147581A 147581B 268711A 159830 135311 135316 267110 249951 733010 Option Parts 135314 152302 268711B TYPE A Part For Plasma Model Part For Plasma Model 352116 352115 ...

Страница 59: ...service purposes LGE Internal Use Only 1 Indoor Unit 346810 35211B 135516 W0CZZA 263232 352150 145200 146811 354210 263230 264110 268711C 131410 149304 359011 342800 147581A 147581B 268711A 135311 135316 267110 249951 733010 Option Parts 135314 152302 268711B TYPE A 352116 352115 ...

Страница 60: ...nal Use Only 1 Indoor Unit 346810 35211B 135516 352150 145200 146811 354210 131410 149304 359011 342800 147581A 147581B 268711A 135311 135316 267110 733010 152313 Option Parts 135314 152302 249951 268711B 268711C W0CZZA 268711D 263230 264110 TYPE B Part For Plasma Model Part For Plasma Model 352116 352115 ...

Страница 61: ...nternal Use Only 1 Indoor Unit 346810 35211B 135516 352150 145200 146811 354210 131410 149304 359011 342800 147581A 147581B 268711A 135311 135316 267110 733010 Option Parts 135314 152302 249951 268711B 268711C W0CZZA 268711D 263230 264110 TYPE B Part For Plasma Model Part For Plasma Model 352116 352115 ...

Страница 62: ...nal Use Only 1 Indoor Unit 346810 35211B 135516 352150 145200 146811 354210 131410 149304 359011 342800 147581A 147581B 268711A 135311 159830 135316 267110 733010 Option Parts 135314 152302 249951 268711B 268711C W0CZZA 268711D 263230 264110 TYPE B Part For Plasma Model Part For Plasma Model 352116 352115 ...

Страница 63: ... Use Only 1 Indoor Unit 346810 35211B 135516 352150 145200 146811 354210 131410 149304 359011 342800 147581A 147581B 268711A 135311 159830 135316 267110 733010 Option Parts 135314 152302 249951 268711B 268711C W0CZZA 268711D 263230 264110 266090 TYPE B Part For Plasma Model Part For Plasma Model 352116 352115 ...

Страница 64: ... reserved Only for training and service purposes LGE Internal Use Only 2 Outdoor unit 554031 552102 437212 435511 W0CZZB 268711F 554160 552560 550140 552203A 552203B 430411 447910 649950 549610 437211 559010 546810 435512 552111 435301 349480 W6631 ...

Страница 65: ... reserved Only for training and service purposes LGE Internal Use Only 2 Outdoor unit 554031 552102 437212 435511 W0CZZB 268711F 554160 552560 550140 552203A 552203B 430411 447910 649950 549610 437211 559010 546810 435512 552111 435301 349480 W6631 ...

Страница 66: ...l right reserved Only for training and service purposes LGE Internal Use Only 2 Outdoor unit 554031 552102 437212 435511 W0CZZB 268711F 554160 550140 552203A 552203B 430411 447910 649950 549610 437211 559010 546810 435512 552111 435301 349480 ...

Страница 67: ...l right reserved Only for training and service purposes LGE Internal Use Only 2 Outdoor unit 554031 552102 437212 435511 W0CZZB 554160 552560 550140 552203A 552203B 430411 447910 649950 549610 437211 559010 546810 435512 552111 435301 349480 ...

Страница 68: ...nly for training and service purposes LGE Internal Use Only 2 Outdoor unit 554031 437212 435511 W0CZZB 554160 552560 550140 552203A 552203B 430411 447910 649950 549610 437211 559010 546810 435512 435301 349480 552111 552201 552102A 552102B 552202 552116 561410 ...

Страница 69: ...c All right reserved Only for training and service purposes LGE Internal Use Only 2 Outdoor unit 554031 552102 437212 435511 W0CZZB 554160 550140 552203A 552203B 430411 447910 649950 549610 437211 559010 546810 435512 552111 435301 349480 ...

Страница 70: ...P NO 3828A20173B APRIL 2009 ...

Отзывы: