- 21 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1) Selection of the best location
1. Indoor unit
• Do not have any heat or steam near the unit.
• Select a place where there are no obstacles in front of
the unit.
• Make sure that condensation drainage can be conve-
niently routed away.
Do not install near a doorway.
• Ensure that the space around the left and right of the
unit is more than "A". The unit should be installed as
high on the wall as possible, allowing a minimum of
"B" from ceiling.
• Use a stud finder to locate studs to prevent unneces-
sary damage to the wall.
2. Outdoor unit
• If an awning is built over the unit to prevent direct sun-
light or rain exposure, make sure that heat radiation
from the condenser is not restricted.
• Ensure that the space around the back and sides is
more than 10cm. The front of the unit should have
more than 70cm of space.
• Do not place animals and plants in the path of the
warm air.
• Take the air conditioner weight into account and select
a place where noise and vibration are minimum.
• Select a place so that the warm air and noise from the
air conditioner do not disturb neighbors.
2) Piping length and elevation
Installation
1. Installation of indoor, Outdoor unit
More than "A"
More than "B"
More than 2.3m
More than "B"
More than 10cm
More than 10cm
More
than 60cm
More than 60cm
More than 70cm
Install the indoor unit on the wall where the height
from the floors more than 2.3 meters.
CAUTION
• Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
• Oil trap should be installed every 5~7 meters.
CAUTION
Grade
Clearance(cm)
A
B
7K~28K
10
5
30K~38K
30
12
Pipe Size
Capacity
(Btu/h)
GAS
LIQUID
Max.
Length
A
(m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B
(m)
Standard
Length
(m)
7k~14k
3/8"(Ø9.52)
1/4"(Ø6.35)
4 or 7.5
7
15
20
1/2"(Ø12.7)
1/4"(Ø6.35)
4 or 7.5
7
15
20
1/2"(Ø12.7)
1/4"(Ø6.35)
4 or 7.5
15
30
20
18k~28k
5/8"(Ø15.88)
1/4"(Ø6.35)
4 or 7.5
15
30
20
5/8"(Ø15.88)
3/8"(Ø9.52)
4 or 7.5
15
30
30
30k~38k
5/8"(Ø15.88)
3/8"(Ø9.52)
7.5
15
30
30
3/4"(Ø19.05)
3/8"(Ø9.52)
7.5
15
30
50
If case more than 5m
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
I
Содержание LS-C082QMA0
Страница 70: ...P NO 3828A20173B APRIL 2009 ...