128 | MULTI F OUTDOOR UNIT
Multi F and Multi F MAX Heat Pump System Engineering Manual
MULTI
F
MAX
MULTI
F
Connected Indoor
Units
Combination
Capacity
Index
Outdoor Air
Temp. (°F
DB)
Indoor Air Temp. °F DB / °F WB
68 / 57
73 / 61
77 / 64
80 / 67
86 / 72
90 / 75
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
Two (2) Ducted
Indoor Units
12 + 12
14
20.59
1.41
21.86
1.46
23.14
1.52
24.07
1.53
25.70
1.56
26.98
1.59
20
20.57
1.43
21.85
1.48
23.13
1.54
24.05
1.56
25.68
1.58
26.96
1.62
25
20.55
1.45
21.83
1.50
23.11
1.56
24.03
1.58
25.66
1.61
26.94
1.64
30
20.54
1.47
21.81
1.53
23.09
1.58
24.01
1.60
25.64
1.63
26.92
1.66
35
20.52
1.49
21.80
1.55
23.07
1.60
23.99
1.62
25.62
1.65
26.90
1.69
40
20.51
1.51
21.78
1.57
23.05
1.62
23.97
1.64
25.60
1.67
26.88
1.71
45
20.49
1.53
21.76
1.59
23.04
1.65
23.96
1.67
25.58
1.70
26.86
1.73
50
20.48
1.55
21.75
1.61
23.02
1.67
23.94
1.69
25.56
1.72
26.83
1.75
55
20.46
1.57
21.73
1.63
23.00
1.69
23.92
1.71
25.54
1.74
26.81
1.78
60
20.44
1.59
21.71
1.65
22.98
1.71
23.90
1.73
25.52
1.76
26.79
1.80
65
20.43
1.61
21.70
1.67
22.97
1.73
23.88
1.75
25.50
1.79
26.77
1.82
70
20.41
1.63
21.68
1.69
22.95
1.76
23.86
1.78
25.48
1.81
26.75
1.85
75
19.92
1.72
21.19
1.79
22.45
1.85
23.36
1.87
24.98
1.91
26.25
1.95
80
19.43
1.81
20.69
1.88
21.95
1.94
22.87
1.97
24.48
2.00
25.74
2.04
85
18.94
1.90
20.20
1.97
21.46
2.04
22.37
2.06
23.98
2.10
25.24
2.14
90
18.46
1.99
19.71
2.06
20.97
2.13
21.87
2.16
23.48
2.20
24.73
2.24
95
17.93
2.07
19.18
2.15
20.43
2.23
21.00
2.25
22.93
2.30
24.17
2.34
100
17.49
2.16
18.74
2.24
19.99
2.32
20.73
2.35
22.49
2.39
23.74
2.44
105
17.06
2.25
18.30
2.33
19.55
2.42
20.46
2.45
22.05
2.49
23.30
2.54
110
16.62
2.34
17.87
2.42
19.12
2.51
20.02
2.54
21.62
2.59
22.86
2.64
115
16.18
2.43
17.43
2.52
18.68
2.61
19.58
2.64
21.18
2.69
22.43
2.74
118
15.92
2.48
17.17
2.57
18.42
2.66
19.32
2.70
20.92
2.75
22.17
2.80
122
15.83
2.55
17.08
2.64
18.33
2.74
19.23
2.77
20.83
2.82
22.08
2.88
9 + 18
14
23.16
1.57
24.60
1.62
26.04
1.68
27.07
1.70
28.91
1.73
30.35
1.77
20
23.14
1.59
24.58
1.65
26.02
1.71
27.05
1.73
28.89
1.76
30.33
1.79
25
23.12
1.61
24.56
1.67
26.00
1.73
27.03
1.75
28.87
1.78
30.30
1.82
30
23.11
1.63
24.54
1.69
25.98
1.76
27.01
1.78
28.85
1.81
30.28
1.85
35
23.09
1.66
24.52
1.72
25.96
1.78
26.99
1.80
28.82
1.83
30.26
1.87
40
23.07
1.68
24.50
1.74
25.94
1.80
26.97
1.82
28.80
1.86
30.24
1.90
45
23.05
1.70
24.49
1.76
25.92
1.83
26.95
1.85
28.78
1.88
30.21
1.92
50
23.04
1.72
24.47
1.79
25.90
1.85
26.93
1.87
28.76
1.91
30.19
1.95
55
23.02
1.75
24.45
1.81
25.88
1.88
26.91
1.90
28.74
1.93
30.17
1.97
60
23.00
1.77
24.43
1.83
25.86
1.90
26.89
1.92
28.71
1.96
30.14
2.00
65
22.98
1.79
24.41
1.86
25.84
1.92
26.87
1.95
28.69
1.98
30.12
2.02
70
22.97
1.81
24.39
1.88
25.82
1.95
26.85
1.97
28.67
2.01
30.10
2.05
75
22.41
1.91
23.84
1.98
25.26
2.05
26.29
2.08
28.10
2.12
29.53
2.16
80
21.86
2.01
23.28
2.08
24.70
2.16
25.72
2.18
27.54
2.22
28.96
2.27
85
21.31
2.11
22.73
2.18
24.14
2.26
25.17
2.29
26.98
2.33
28.39
2.38
90
20.76
2.21
22.18
2.29
23.59
2.37
24.61
2.40
26.41
2.44
27.83
2.49
95
20.17
2.30
21.58
2.39
22.98
2.47
23.63
2.50
25.79
2.55
27.20
2.60
100
19.68
2.40
21.08
2.49
22.49
2.58
23.32
2.61
25.30
2.66
26.70
2.71
105
19.19
2.50
20.59
2.59
22.00
2.68
23.01
2.72
24.81
2.77
26.21
2.82
110
18.70
2.60
20.10
2.69
21.51
2.79
22.52
2.82
24.32
2.87
25.72
2.93
115
18.21
2.69
19.61
2.79
21.02
2.90
22.03
2.93
23.83
2.98
25.23
3.04
118
17.91
2.75
19.32
2.85
20.72
2.96
21.74
2.99
23.53
3.05
24.94
3.11
122
17.81
2.83
19.22
2.94
20.62
3.04
21.64
3.08
23.43
3.13
24.84
3.20
PERFORMANCE DATA
Cooling Capacity Tables
Table 121:
LMU36CHV Cooling Capacity Table — Ducted Indoor Units (continued)
TC = Total Capacity (kBtu/h).
PI = Power Input (kW).
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table rows indicate reference data. When operating at this temperature, these values can
be different if the system is not running consistently.