Refrigeration Cycle Diagram
LM-4462H2T
(
■
Rated performance for refrigerant line length of: 7.5m)
For installation over rated distance, 70g of refrigerant should be added for each meter in Heat pump Model.
For installation over rated distance, 50g of refrigerant should be added for each meter in Cooling only Model.
ex) When installed at a distance of 15m, 525g of refrigerant should be added in Heat pump Model.
(15-7.5) x 70g = 525g
When installed at a distance of 15m, 375g of refrigerant should be added in Cooling only Model.
(15-7.5) x 50g = 375g
Pipe size(Diameter: ø)
Piping length(m)
Elevation(m)
Gas
Liquid
Rated
Max.
Rated
Max.
5/8"
3/8"
7.5
50
7.5
30
–7–
INDOOR A-UNIT
INDOOR B-UNIT
OUTDOOR UNIT
HEAT
EXCHANGER
HEAT
EXCHANGER
HEAT
EXCHANGER
A-COMPRESSOR
GAS SIDE
LIQUID SIDE
COOLING
HEATING
A-REVERSING
VALVE
CAPI
CAPI
CAPILLARY TUBE
HEAT
EXCHANGER
B-COMPRESSOR
GAS SIDE
LIQUID SIDE
B-REVERSING
VALVE
CAPILLARY TUBE