–24–
Air conditioner
unit
Ceiling
board
Cassette trim
Cassette trim
Fit the insulator (this part) and
be careful for cool air leakage
Good example
Air
Cool air leakage
(no good)
Bad example
Ceiling
board
Air conditioner unit
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
1/50~1/100
MAX 700mm
CAUTION
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
• Connect the main drain pipe to the exterior
and leave it provisionally until the test comes
to an end.
• Feed water to the flexible drain hose and
check the piping for leakage.
• Be sure to check the drain pump for normal
operating and noise when electrical wiring is
finished.
• When the test is completed, connect the flexi-
ble drain hose to the drain port on the indoor
unit.
Heat insulation material: Polyethylene foam with
thickness more than 8 mm.
8. Indoor Unit Drain Piping
Drain test
Install certainly the cassette trim.
Cool air leakage causes sweating.
Water drops fall.
• Drain piping must have down-slope (1/50 to 1/100):
be sure not to provide up-and-down slope to prevent
reversal flow.
• During drain piping connection, be careful not to
exert extra force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the
indoor unit is 32mm.
• Be sure to install heat insulation on the drain piping.
Содержание LM-4462C2T
Страница 1: ...SERVICE MANUAL Ceiling Cassette Multi Air Conditioner MODELS LM 4462H2T LM 4462C2T ...
Страница 38: ... 38 Electronic control device MAIN P C B ASM ...
Страница 39: ... 39 2 MAIN P C B ASM OUTDOOR ...
Страница 42: ... 42 ...
Страница 50: ...Memo 50 ...
Страница 51: ...P No 3828A20197A January 2002 Printed in Korea ...