Performance data
— 6 —
Table-1
Supply Fan Performance LK-0580HC/0580CC(SI)
• Fan motor heat = 2 x BkW
• Test Condition:
➊
Voltage : 380V
❷
Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
L/s
High Speed
ESP
BkW
802
849
897
944
991
1038
1085
1133
22.27
19.68
17.09
14.49
11.90
9.30
6.71
4.12
0.38
0.41
0.45
0.48
0.52
0.56
0.59
0.63
21.19
17.25
13.32
9.39
5.46
1.53
-
-
0.33
0.37
0.40
0.43
0.47
0.50
-
-
7.52
0.75
-
-
-
-
-
-
0.38
0.42
-
-
-
-
-
-
ESP
BkW
ESP
BkW
Mid Speed
Low Speed
Table-2
Supply Fan Performance LK-0580HC/0580CC (English)
• Fan motor heat(MBH)= 5.09 x Fan Bhp
• Test Condition:
➊
Voltage :380V
❷
Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
CFM
High Speed
ESP
BHP
1,700
1,800
1,900
2,000
2,100
2,200
2,300
2,400
0.85
0.77
0.67
0.57
0.51
0.41
0.26
0.11
0.54
0.55
0.59
0.65
0.67
0.72
0.80
0.89
0.79
0.68
0.59
0.37
0.23
0.06
-
-
0.44
0.49
0.54
0.58
0.63
0.67
-
-
0.30
0.03
-
-
-
-
-
-
0.51
0.56
-
-
-
-
-
-
ESP
BHP
ESP
BHP
Mid Speed