Installation Manual 7
ENGLISH
Installation of Indoor, Outdoor Unit
3. Piping length and the elevation
Gas
Liquid
Standard
Max.
Standard
Max.
24k Btu/h
1/2"(12.7mm) 1/4"(6.35mm)
7.5(25')
30(100')
5(16')
15(50')
20(0.22 oz./ft.)
34k Btu/h 5/8"(15.88mm) 1/4"(6.35mm)
7.5(25')
35(115')
5(16')
20(66')
30(0.32 oz./ft.)
Capacity
Pipe Size
Length A(m)
Elevation B(m)
*Additional
(Diameter:Ø)
refrigerant(g/m)
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
If piping length is more than 5m
Outdoor unit
Indoor unit
B
CAUTION:
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.