12 | Product data
Art Cool
™
Premier W
all Mounted Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
Model number
nominal Tons
Compressor
Qty.
Compressor (A)
Cool/Heat
Fan Qty.
oDU Fan (A) IDU Fan (A)
MCA(A)
MoP(A)
LA090HYV1
3/4
1
8.3/8.3
1
0.40
0.40
11.2
15
LA120HYV1
1
1
8.3/8.3
1
0.40
0.40
11.2
15
Table 3: Single-Zone Art Cool Premier System Electrical Data Table.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum overcurrent Protection (MoP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
eleCTriCAl dATA