Service Manual 49
Installation
• Total main pipe(A) = 30m
• Each branch pipe(a, b, c) = 10m
• Additional Charge = (30-5)m x 60g/m
+ (10-5)m x 30g/m x 3
= 1950g
A
a
Circuit 1
b
c
18k
18k
18k
d
e
24 k
24 k
B
The calculation of the additional charge should take account of the length of pipe.
Additional charge (g)
Total Main pipe length - rated length
x 60g/m
12k Branch pipe length - rated length
x 20g/m
18k~36k Branch pipe length - rated length
x 30g/m
=
+
+
❈
Rated length = Main pipe : 5m
Branch pipe : 7.5m
• Total main pipe(B) = 30m
• Each branch pipe(d, e) = 10m
• Additional Charge = (30-5)m x 60g/m
+ (10-5)m x 30g/m x 2
= 1800g
Additional Charge of Circuit 1
Additional Charge of Circuit 2
Circuit 2
Indoor Unit Capacity
Pipe Size
Rated
Max
Additional
(Btu/h)
Gas
Liquid
Length Length
Refrigerant
48k
3/4"(19.05mm) 3/8"(9.52mm)
7.5m
50m
60g/m
❋
Extra refrigerant per circuit = (Extended length - Rated length) x Additional refrigerant
■
Refrigerant Charge
• Direct Piping Circuit
• Distributor Piping Circuit
Содержание L8UC100BFA0
Страница 92: ...92 Multi type Air Conditioner Schematic Diagram 2 Outdoor Unit 1 L8UC100BFA0 L8UH100BFA0 ...
Страница 95: ...Service Manual 95 L8UH100BFA0 L8UC100BFA0 Schematic Diagram 2 Outdoor Unit ...
Страница 97: ...Service Manual 97 2 Duct Type High static BH BG BE chassis Schematic Diagram ...
Страница 98: ...98 Multi type Air Conditioner Schematic Diagram Low static BT BT1 chassis ...
Страница 99: ...Service Manual 99 4 way TE TF TD chasis 58 B Schematic Diagram ...
Страница 100: ...100 Multi type Air Conditioner Schematic Diagram 2 Display ASSEMBLY 1 Split Type ...
Страница 153: ...P No 3828A22009L October 2005 Printed in Korea ...