Installation Manual
7
Installation of Indoor, Outdoor Unit
Installation of Indoor, Outdoor Unit
Selection of the best location
1) Indoor unit
Select location
Install the air conditioner in the location that satisfies
the following conditions.
• The place shall easily bear a load exceeding four
times the indoor unit’s weight.
• The place shall be able to inspect the unit as the
figure.
• The place where the unit shall beleveled.
• The place shall allow easy water drainage.(Suitable
dimension “H” is necessary to get a slope to drain
as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an
electrical noise.
• The place where air circulation in the room will be
good .
• There should not be any heat source or steam near
the unit
2) Outdoor unit
• If an awning is built over the unit to prevent
direct sunlight or rain exposure, be careful that
heat radiation from the condenser is not
restricted.
• There should not be any animals or plants
which could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from
the wall, ceiling, fence or other obstacles.
3) Piping length and the elevation
Indoor unit
Outdoor unit
B
A
H
600
600
Top view
(unit: mm)
Front view
Front
Inspection hole
(600X600)
Control box
1000
More than
90cm
More than 90cm
More than 120cm
More than 90cm
More than
90cm
Fence or
obstacles
Fence or
obstacles
Fence or
obstacles
• Capacity is based on standard length and
maximun allowance length is on the basis of
reliability.
• Improper refrigerant charge may result in
abnormal cycle.
30
40
7.5
7.5
15
15
30
30
Gas
1/2
5/8
Liquid
1/4
1/4
*Additional
refrigerant
(g/m)
Standard
Length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Pipe Size
(Diameter: Ø)
Model
L2-C366BA0
L2-C486BA0