2020/07/23 page 15
ENTERING THE “POWER CODE SETTING” MODE
2.
Hold the SETTINGS button for 5 s.
-
The display shows the set power code in
kW
.
-
The power code can be changed by shortly pressing the SETTINGS button. It changes cyclically
according to the following table
Cooling
power
kW
05
07
10
12
14
16
22
28
Btu
18
24
36
42
48
60
80
100
kW
33
39
45
50
56
62
67
73
Btu
120
140
160
180
200
220
240
260
ENTERING THE “MODBUS ADDRESS SETTING” MODE
3.
Hold the SETTINGS button for 5 s.
-
The display shows the set address for MODBUS communication. This address is also usable for LG
central control systems.
The MODBUS address can be changed by briefly pressing the SETTINGS button. It changes
cyclically from 90 to A7. (90 = service communication; 91,…, A7 = MODBUS communication)
Address
90
91
92
93
94
95
96
97
99
9A
9B
9C
9D
9E
9F
A0
A1
A2
A3
A4
A5
A6
A7
ENTERING THE “PROGRAM SELECTION” MODE
4.
Hold the SETTINGS button for 5 s
-
The display shows the setting of the active program
“0“.
-
Service settings
–
do not change the program
5.
Hold the SETTINGS button for 5 s to return to point 2.
If you do not press the SETTINGS button for 10 seconds, the last set value is automatically saved, the setting
mode is exited and the initial information sequence appears on the display.
Attention! After changing the settings, it is necessary to restart the outdoor unit (restore power). If
the outdoor compressor unit is not restarted, the changes are not accepted by the unit.
SETTING THE INTERNAL SYSTEM ADDRESS (AUTO-ADRESSING PROCESS)
When starting the system for the first time, it is necessary to perform auto-addressing of the system
–
see the
relevant installation manual for the outdoor compressor unit. During the addressing process, the “
- -
“ symbol
appears on the display. After the addressing is completed, the display shows the assigned module address in
hexadecimal format (for approx. 10s).
The assigned address is displayed in the introductory information sequence:
1
st
cycle - basic hardware and software setting information
–
example:
“LG … Ar … 56 … So …
4.3
…S
o
… 3“
Explanation
–
module designed to communicate with the compressor unit, model series ARUM/N, power code
set to 56kW, software version 4.3, user software 3
2
nd
cycle - basic hardware and software setting information
–
example
:
“LG … Ar … 56 … So …
4.3
…
So
… 3 … 11“