
Hydro Kit
Installation Manual
15
ENGLISH
Installation
Strainer
- Use the 50 mesh strainer.
(Exclude scale diameter of 0.4mm or less and other net)
- Check the strainer direction and assemble on the inlet hole (Refer to picture)
- Wrap the Teflon tape on the screw thread of the water pipe for more than 15 times for assembly.
- Install the service port facing downward. (Within left/right 45 degrees)
- Check if there is any leakage on the connecting part.
- Clean the strainer periodically. (Once a year or more frequent)
Water In
Strainer
Side
Front
45°
Содержание Hydro Kit ARNH04GK2A4
Страница 62: ...62 Hydro Kit ...
Страница 63: ......