38
INSTALLATION OF INDOOR UNIT
ENGLISH
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1.5 2.0 2.5 3.0
A
min
(m
2
)
m
c
(kg)
Total Ref.
Amount
m
c
(kg)
Minimum Floor Area
A
min
(m
2
)
Based on
h
0
1.2m
1.84
7.20
1.86
7.36
1.88
7.52
1.90
7.68
1.92
7.84
1.94
8.01
1.96
8.17
1.98
8.34
2.00
8.51
2.02
8.68
2.04
8.85
2.06
9.03
2.08
9.21
2.10
9.38
2.12
9.56
2.14
9.74
2.16
9.93
2.18
10.11
2.20
10.30
2.22
10.49
2.24
10.68
2.26
10.87
2.28
11.06
2.30
11.26
2.32
11.45
2.34
11.65
2.36
11.85
2.38
12.05
2.40
12.26
2.42
12.46
2.44
12.67
2.46
12.88
2.48
13.09
2.50
13.30
2.52
13.51
2.54
13.73
2.56
13.94
2.58
14.16
2.60
14.38
2.62
14.61
2.64
14.83
2.66
15.05
2.68
15.28
2.70
15.51
NOTE
• The value of "Release height (h
0
)“ in this
unit is considered 1200 mm to comply
to IEC 60335-2-40:2013
A1 2016 Clause GG2.
• For intermediate m
c
values, the value
that corresponds to the higher m
c
value
from the table is considered.
(If m
c
= 1.85 kg, the value that
corresponds to mc = 1.86 kg is
considered.)
• Systems with total refrigerant charge
lower than 1.84 kg are not subjected to
any room area requirements.
• Charges above 2.70 kg are not allowed
in the unit.
Table 2 - Minimum floor area