INSTALLER SETTING
ENGLISH
Function
Description
Cooling temp. setting
At the water control in cooling mode, the control reference
water temperature position setting.
Air cooling set temp.
Adjusting range of 'Setting Air Temperature' in cooling mode.
Water cooling set temp.
Adjusting range of 'Setting Leaving Water Temperature' in
cooling mode.
Water supply off temp. during
cooling
Determine the leaving water temperature which blocks the
flow into underfloor coil in cooling mode.
TH on/off Variable, cooling water Cooling Water Outlet Temperature TH On / Off Type.
Pump setting in cooling
Set water pump on/off interval option during thermo off
condition in cooling mode.
Room Cooling
Function
Description
DHW set temp.
Setting DHW set temperature.
Tank disinfection setting 1
Setting start/maintain time for disinfection.
Tank disinfection setting 2
Setting disinfection temperature.
Tank setting1
Setting minimum and maximum temperature using heat
pump cycle for DHW heating.
Tank setting2
Setting temperature hysteresis.
DHW time setting
Determine follow time duration : operation time of domestic
hot water tank heating, stop time of domestic hot water tank
heating, and delay time of DHW tank heater operating.
Domestic Hot Water
Function
Description
Pump test run
Main water pump test run.
Frost Protection Temp.
the function is to apply an offset to the freezing temperature
of the freeze protection logic when using antifreeze mode.
Service
Function
Description
Seasonal auto temp
Set the operating temperature in Seasonal Auto mode.
Auto Mode