SERVICING PRECAUTIONS

-3-

Features of refrigerant (R600a)

• Achromatic and odor less gas.
• Flammable gas and the ignition (explosion) at 494°C.
• Upper/lower explosion limit: 1.8%~8.4%/Vol. 

Features of the R600a refrigerator

• Charging of 60% refrigerant compared with a R134a model
• The suction pressure is below 1bar (abs) during the operation.
• Because of its low suction pressure, the external air may flow in the cycle

system when the refrigerant leak, and it causes malfunction in the compressor.

• The displacement of compressor using R600a must be at least 1.7 times larger

than that of R134a.

• Drier type is XH-9.
• The EVAPORATOR or any other cycle part that has welding joint is hidden in

the foam. (If not hidden inside, the whole electric parts must be tested with the
LEAKAGE TEST according to the IEC Standard.)

• The compressor has label of the refrigerant R600a.
• Only the Service  man must have an access to the system.

Installation place

• Must be well ventilated.
• Must be 20 m

3

or larger.

• Must be no-smoking area.
• No ignitable factors must be present.

Utilities

• Refrigerant cylinder (MAX NET 300g)
• Manometer
• Vacuum pump (600L/min)
• Piercing Clamp
• Quick coupler
• Hoses (5m-1EA, 1m-3EA)
• LOKRING
• Portable Leakage detector (3g/year¯)
• Nitrogen cylinder (for leakage test)
• Concentration gauge

Make sure before Servicing

• Refrigerant

Confirm the refrigerant by checking Name Plate on innerliner and the label on
the compressor.

• If the refrigerant is R600a, you must not weld or apply a heat source.

Air Recharging in Compressor

Before refilling the refrigerant, you must perform the test according to Chapter 5
(TROUBLESHOOTING CHART). When the defects are found, you must
discharge the residual refrigerant (R600a) in the outdoor. For discharging the
refrigerant R600a, break the narrow portion of tube extension by hand or with a
pipe cutter as shown in Figure 1. Leave it for 30min in outside to stabilize the
pressure with ambient. Then, check the pressure by piercing the dryer part with
piercing pliers. If the refrigerant is not completely discharged, let the refrigerator
alone for more 30min in outside.

Attach the service tube installed with a Schrader valve (one-way
valve) by using the LOKRING (Figure 2). Then, connect the
Schrader valve (one-way valve) to the pump that is connected to
the discharging hose leading to the outside. When discharging the
residual refrigerant, repeat 3 cycle that includes 3min of the pump
running->pump off->30sec of the compressor running.

After the refrigerant (R600a) is completely discharged, repair any
defective parts and replace the dryer. At any case you must use the
LOKRING for connecting or replacing any part in the cycle (No Fire,
No Welding). Connect the Schrader valve to pump with the coupler.
And then turn the pump on for vacuum state (Figure 3). Let the
pump run until the low-pressure gauge indicates the vacuum (gauge
pressure 0, absolute pressure -1atm or -760mmHg). Recommended
vacuum time is 30 min. Charge the N2 gas in order to check for
leakage from welding points and the LOKRING. If leakages are
found, repair the defects and repeat the vacuum process.

After the system is completely vacuumed, fill it with the refrigerant
R600a up to what has been specified at your refrigerator Name
Plate. The amount of refrigerant (R600a) must be precisely
measured within the error of ±1g by an electron scale (Figure 4).

If you use the manifold connected with both the refrigerant
(R600a) cylinder and the vacuum pump simultaneously,
make sure the pump valve is closed (Figure 5).

Connect the charging hose (that is connected to the refrigerant (R600a) cylinder) to
the Schrader valve installed on the service tube. Then, charge the refrigerant (R600a)
by controlling the Throttle valve. When you do so, do not fully open the Throttle valve
because it may make damage to the compressor. Gradually charge the refrigerant
(R600a) by changing open and close the Throttle Valve (5g at each time). The
charging hose must use a one-way valve to prevent the refrigerant refluence. Close
the Schrader valve cap after the refrigerant (R600a) is completely recharged.

After you completely recharge the refrigerant (R600a), perform the leakage test by
using a portable leakage detector or soapy water. 
Test the low pressure (suction) parts in compressor off time and high pressure parts
in compressor on time. If the leakages are found, restart from the refrigerant (R600a)
discharging process and repairs defects of leaks.

After the leakage test, check the temperature of each parts of the cycle. Check with
hands if the CONDENSER and the case (HOT-LINE pipe) that is contacted to the
door gasket are warm. Confirm that frost is uniform distributed on the surface of
the freezer room and the back wall of fridge room.

POINT TO BE 
BROKEN

CHARGE TUBE 
EXTENSION

SCHRADER VALVE
(ONE-WAY VALVE)

LOKRING

SERVICE TUBE 
EXTENSION

Figure  1

Figure  2

TO THE 
VACUUM 
PUMP

PRESSURE 
GAUGE

Figure  3

WEIGH SCALE

THROTTLE 
VALVE

COUPLE

REFRIGERANT
(R600a)

CHARGING HOSE

Figure  4

FILLING OR 
CHARGE TUBE

VALVE TO BE OPENED 
WHEN REFILLING

VALVE TO BE CLOSED 
AFTER VACUUM

TO THE VACUUM PUMP

TO THE 
REFRIGERATION
SYSTEM

TO THE CHARGE 
CYLINDER

Figure  5

Содержание GR-154 series

Страница 1: ...REFRIGERATOR SERVICE MANUAL CAUTION BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL COLOR SUPER WHITE http biz lgservice com MODEL GR 154 Ref No GR 154 ...

Страница 2: ...o prevent electric shock 4 If you use any kind of appliance check regular current voltage and capacity 5 Don t touch deep frozen products in the freezer with wet hands This may cause frostbite 6 Prevent water from following onto electric elements in the mechanical parts 7 When tilting the set remove any materials on the set especially the thin plates ex Glass shelf or books 8 Leave the disassembly...

Страница 3: ...ace the dryer At any case you must use the LOKRING for connecting or replacing any part in the cycle No Fire No Welding Connect the Schrader valve to pump with the coupler And then turn the pump on for vacuum state Figure 3 Let the pump run until the low pressure gauge indicates the vacuum gauge pressure 0 absolute pressure 1atm or 760mmHg Recommended vacuum time is 30 min Charge the N2 gas in ord...

Страница 4: ... TOTAL 100 DIMENSIONS mm 550 W X 600 D X 850 H NET WHIGHT kg 40 TEMPERATURE CONTROL BUTTON DEFROSTING SYSTEM MANUAL OUT CASE Coated Steel sheet INNER CASE ABS INSULATION CYCLOPENTANE ITEMS SPECIFICATIONS DRAWER 4EA ICE TRAY COMPRESSOR P T C Starting Type CONDENSER Wire Condenser REFRIGERANT R600a 40g LUBRICANT OIL HTS 60 MT 210cc ITEMS SPECIFICATIONS YES ...

Страница 5: ...efitting the door swap the Hinge Cap by pulling it out from its current location and repositioning it on the other side of the door Care should be taken not to damage the adjacent surfaces when removing the Hinge Cap 5 Unscrew the Upper Hinge pin U and screw it into the opposite side hole 6 After refitting the door fix the Lower Hinge L in the opposite side by using 2xBOLTS 7 Fix the Leg 8 Careful...

Страница 6: ...tion of the single phase induction motor in the starting operation flows in both main coil and sub coil After the starting is over the current in subcoil is cut off The proper features of PTC play all the above roles So PTC is used as a motor starting device 3 PTC Applied Circuit Diagram According to Starting Method for the Motor 4 Motor Restarting and PTC Cooling 1 For restarting after power off ...

Страница 7: ... heating the heater inside the OLP and the OLP protects Motor by cutting off current which flows to the Compressor Motor 2 Role of the OLP 1 The OLP is attached to the Hermetic Compressor used for the Refrigerator and Show Case and prevents the Motor Coil from being started in the Compressor 2 Do not turn the Adjust Screw of the OLP in any way for normal operation of the OLP Composition and connec...

Страница 8: ...ting voltage 10 Advice the customer to use in the specified range If not 0 or Advice the customer to use in the specified range Measure minimum starting voltage after checking steps 1 3 above Measure the pressure balance of the PTC at the interval of more than 5 min Starts at the voltage of more than 90 Replace OLP Normal Normal Replace the PTC Replace the PTC STARTER The applied voltage is not in...

Страница 9: ... PTC with a multitester or Wheatstone Bridge Observation value is 220 240V 50Hz 33Ω 20 The value is 0 The value is Check another electric components Replace the PTC Normal Abnormal Abnormal Replace the PTC Separate the OLP from the Compressor and check resistance value between two terminals of OLP with Tester Check other electric components Replace OLP ...

Страница 10: ...n 30 min Poor contacting point Shorted or Broken Coil shorted Low voltage Increase the voltage Replace the device Repair the Compressor Shorted Poor contacting point and broken Refrigerant leaks Poor compressing Check the current flowing of starting system Check the components on the main circuit Check if the current flows at the contacting point of the Thermostat Check if the current flows at the...

Страница 11: ...ts connecting the various components or in an eventual hole in the evaporator made by the user If in the refrigerant system a quantity of R600a is introduced which is greater than that indicated the excess gas does not terminate its expansion in the evaporator but proceeds into the return tube The refrigerant system is humid when there is a small percentage of water present which not completely re...

Страница 12: ...eep the drier in a outdoors because ASM 1 after unpacking humidity damages to it 2 Keep the unpacked drier at the temperature of 80 100 C VACUUM 1 When measuring with pirant Vacuum Apply M C Vacuum Gauge without fail 1 gauge the charging M C vacuum Perform vacuum operation until a proper 1 degree is within 1 Torr vacuum degree is built up 2 If the vacuum degree of the cycle inside is If a proper v...

Страница 13: ... 14 ASSEMBLY JAWS BOLT TOOL TUBE LOKRING LOKRING JOINT Figure 15 LOKRING Figure 16 LOKRING TOOL ...

Страница 14: ...501A ...

Страница 15: ...136D ...

Страница 16: ...P NO 3828JD8401A ...

Отзывы: