REGULAR MAINTENANCE
ENGLISH
83
CAUTION
• In order to cool down completely, stop the unit 1~2 hours prior to maintenance/replace-
ment. If you touch a heated area of the outdoor unit parts which was in operation, it may
cause burns.
• Make sure to shut off the power breaker of the outdoor control panel when performing
internal work on the outdoor unit. If the indoor unit is operated by the customer’s remote
control during internal work, it may cause injury or equipment damage.
• Use authentic products from LG electronics for the parts replacement. Use of inauthentic
parts or oil can cause malfunction of the unit and the customer will be responsible for any
damages involved.
!
h
Compressor drive belt replacement
- The drive belt should be replaced every 10,000 hours or 5 years. (whichever comes first)
- Use authentic products from LG electronics for the drive belt replacement.
- (caution) Stop the engine by controlled shutdown before the maintenance. (refer to 'Opera-
tion restriction of the outdoor unit prior to maintenance' in the 'Self-diagnosis')
Refer to the table below when preparing the tools and part required for the replacement/mainte-
nance.
Necessary parts
and tools
Specifications and
Stock No.
Quantity
Remarks
Drive belt
10 RIB
1
LG electronics authentic products
Torque wrench
8~200 N·m
1
Socket wrench
10,19,22 mm
1st
Spanner
19 mm
1
Tension Meter
1
U-507
Compressor drive belt replacement
- Loosen the compressor bracket fixing bolt. (refer to Figure1)
Figure 1 Location of the compressor bracket fixing bolt
Compressor drive belt replacement