ADDITIONAL FUNCTIONS
ENGLISH
63
Target Static Pressure Setup
It is used to change the target value of the outdoor unit and adjust it to the purpose of use.
Mode Setup
Dip switch #5 of the outdoor unit ON
Display "Func" on 7-segment using '
▶
', and
'
◀
' buttons, and press the '
●
' button.
Display "Fn8" on 7-segment using '
▶
', and
'
◀
' buttons, and press the '
●
' button.
Target Pressure Change
Display either "OFF", "op1"~"op4" on
7-segment using '
▶
', and '
◀
' buttons, and
press the '
●
' button.
CAUTION
• Ask the licensed installer for the function setup when installing the outdoor unit.
• Set it OFF if you do not use the function.
• The capacity may decline or the power consumption may increase.
!
Target Pressure Setup
mode
Purpose
Condensing temperature
variation
Evaporating temperature
variation
op1
Capacity Improvement Stage 1
-3 °C
+2 °C
op2
Capacity Improvement Stage 2
-1.5 °C
-2 °C
op3
Energy Saving Stage 1
+2.5 °C
-4 °C
op4
Energy Saving Stage 2
-4.5 °C
-6 °C
Содержание GP-W500B6C
Страница 90: ...90 ENGLISH ...
Страница 91: ......