Chapter 2. SPECIFICATIONS
2 - 2
2.2 Performance Specifications
Table 2.2 shows performance specifications of the RTD input module.
Specifications
Item
G3F-RD3A
G4F-RD2A
Connectable RTD
Pt 100 (JIS C1640-1989, DIN 43760-1980)
JPt100 (KS C1603-1991, JIS C1604-1981)
Temperature input range
Pt100
JPt100
: -200.0
°
C to 600
°
C (18.48 to 313.59
Ω
)
: -200.0
°
C to 600
°
C (17.14 to 317.28
Ω
)
Digital output
Digital conversion value : 0 to 16,000
Detected temperature value : -2000 to 6000 (one digit after
point
5
10)
Buffer memory
Each of three wires at every channel has detection
function.
Accuracy
±
0.5 %(full scale)
Maximum conversion speed
50ms per channel
Number of temperature input device points
8 channels per module
4 channels per module
Insulation method
Photo-coupler insulation between the input terminal and
the PLC power supply (non-insulation between channels)
Connection terminal block
38-point terminal block
20-point terminal block
Internal current consumption
0.5 A
0.45A
Weight
630 g
350 g
[Table. 2.2 Performance Specifications]