Chapter 7. DEDICATED INSTRUCTIONS FOR SPECIAL MODULES
7 - 1
Chapter 7. DEDICATED INSTRUCTIONS
FOR SPECIAL MODULES
(Read from /Write to Buffer Memory)
I/O points of the RTD input module are 16.
7.1 Local
7.1.1 Read from Buffer Memory
⋅
⋅
⋅
GET, GETP
<Format>
execution condition
for GET
Format
Descriptions
Available Data Type
n1
The number of the slot where the special modules mounted
Integer
n2
First address of the special module buffer memory from which the
data will be read.
Integer
D
First address of the device to store the data read.
M,P,K,L,T,C,D,#D
n3
Word number of data to be read .
Integer
<The difference between GET and GETP>
GET: always executed if the execution condition turns On.
(
)
GETP : executed if the execution condition is triggered.
(
)
Example 1). In this example, the RTD input module is loaded on the slot 3 in the base
unit and the data of the buffer memory addresses 9, 10 and 11 will be read to the CPU module
addresses D9, D10 and D11.
RTD input module
(address) CPU module D area Buffer memory (address)
D8
D9
Temp conversion Value of Ch 0
Temp conversion Value of Ch 0
D10
Digital conversion Value of Ch 0
Digital conversion Value of Ch 0
D11
Error code of Ch 0
Error code of Ch 0
D12
8
9
10
11
12
<GET>
execution condition
for GET
execution condition
for GETP
<GETP>
M0000
GET n1 n2 D n3
GET 00003 00009 D0009 00003
D M0000
GETP 00003 00009 D0009 00003