INSTALLATION OF OUTDOOR UNIT
7
ENGLISH
Ceiling Cassette <Type : 4Way>
Ceiling Suspended Air conditioner
Floor Standing Air Conditioner
Ceiling Concealed Duct
Ceiling Concealed Duct – Low Static
CHASSIS
CAPACITY
[Btu/h]
Pipe Size [mm (inch)]
Length A [m]
Elevation B [m]
Additional
Refrigerant [g/m]
Gas
Liquid
Standard
Max.
Standard
Max.
UL2
18 K
Ø12.7(1/2)
Ø6.35(1/4)
5
30
5
15
20
U24A
24 K
Ø15.88(5/8)
Ø9.52(3/8)
5
50
5
30
20
U4
36 K
Ø15.88(5/9)
Ø9.52(3/8)
5
50
5
30
20
48 K
Ø19.05(3/4)
Ø9.52(3/8)
5
50
5
30
20
U3
54 K
Ø19.05(3/4)
Ø9.52(3/8)
5
50
5
30
20
CHASSIS
CAPACITY
[Btu/h]
Pipe Size [mm (inch)]
Length A [m]
Elevation B [m]
Additional
Refrigerant [g/m]
Gas
Liquid
Standard
Max.
Standard
Max.
UL2
18 K
Ø12.7(1/2)
Ø6.35(1/4)
5
30
5
15
20
U24A
24 K
Ø15.88(5/8)
Ø9.52(3/8)
5
50
5
30
20
U4
36 K
Ø15.88(5/9)
Ø9.52(3/8)
5
50
5
30
20
48 K
Ø19.05(3/4)
Ø9.52(3/8)
5
50
5
30
20
U3
54 K
Ø19.05(3/4)
Ø9.52(3/8)
5
50
5
30
20
CHASSIS
CAPACITY
[Btu/h]
Pipe Size [mm (inch)]
Length A [m]
Elevation B [m]
Additional
Refrigerant [g/m]
Gas
Liquid
Standard
Max.
Standard
Max.
UL2
18 K
Ø12.7(1/2)
Ø6.35(1/4)
5
30
5
15
20
U24A
24 K
Ø15.88(5/8)
Ø9.52(3/8)
5
50
5
30
20
U4
36 K
Ø15.88(5/9)
Ø9.52(3/8)
5
50
5
30
20
48 K
Ø19.05(3/4)
Ø9.52(3/8)
5
50
5
30
20
U3
54 K
Ø19.05(3/4)
Ø9.52(3/8)
5
50
5
30
20
CHASSIS
CAPACITY
[Btu/h]
Pipe Size [mm (inch)]
Length A [m]
Elevation B [m]
Additional
Refrigerant [g/m]
Gas
Liquid
Standard
Max.
Standard
Max.
U4
36 K
Ø15.88(5/9)
Ø9.52(3/8)
5
50
5
30
20
48 K
Ø19.05(3/4)
Ø9.52(3/8)
5
50
5
30
20
If installed tube is shorter than 5 m, additional charging is not necessary.
Additional Refrigerant = (A - 5) x Additional refrigerant (g)