2008 Product Data
101
14. Installation
Outdoor
1. Remove the control cover from the unit by loosening
the screw.
Connect the wires to the terminals on the control
board individually.
2. Secure the cable onto the control board with the cord
clamp.
3. Refix the control cover to the original position with the
screw.
4. Use a recognized circuit breaker between the power
source and the unit.
A disconnecting device to adequately disconnect all
supply lines must be fitted.
1
(L)
2
(N)
3
Cover control
Cord clamp
Outdoor Unit
Connecting cable
9k~12k
18k
24k
30k~36k
18k S5
15
20
30
25
Circuit
Breaker
(A)
Grade
According to the confirmation of the above conditions, prepare the wiring as follows.
1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control cover.
2. The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3. Specification of power source.
4. Confirm that electrical capacity is sufficient.
5. See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
6. Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.
7. Always install an earth leakage circuit breaker in a wet or moist area.
8. The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal
function of the overload.
9. The means for disconnection from a power supply shall be incorporated in the fixed wiring and have
an air gap contact separation of at least 3mm in each active(phase) conductors.
Содержание AS-W0964GG1
Страница 1: ...5RMA2 01A Inverter Single 50Hz R410A ...
Страница 32: ...2008 Product Data 31 5 Dimensional drawings Indoor units 5 1 Indoor Units ...
Страница 33: ...32 2008 Product Data 5 Dimensional drawings Indoor units ...
Страница 34: ...2008 Product Data 33 5 Dimensional drawings Indoor units ...
Страница 35: ...34 2008 Product Data 5 Dimensional drawings Indoor units 45 140 Ø70 188 926 65 221 45 296 175 Ø70 ...
Страница 36: ...2008 Product Data 35 5 Dimensional drawings Indoor units ...
Страница 40: ...2008 Product Data 39 5 Dimensional drawings Outdoor units 1 5 2 Outdoor Units ...
Страница 41: ...40 2008 Product Data 5 Dimensional drawings Outdoor units 1 ...
Страница 46: ...2008 Product Data 45 6 Wiring diagrams Indoor Unit Models AS W096ADR0 AS W126ADR0 ...
Страница 48: ...2008 Product Data 47 6 Wiring diagrams Indoor Unit Models AS W1868 H1 Models AS W2463 H3 ...
Страница 49: ...48 2008 Product Data 6 Wiring diagrams Indoor Unit Models AS W2468 H1 ...
Страница 52: ...2008 Product Data 51 Models AS W096ADR0 AS W126ADR0 6 Wiring diagrams Outdoor units ...
Страница 54: ...2008 Product Data 53 6 Wiring diagrams Outdoor units Models AS W1865GG1 AS W1863 H3 Models AS W1868 H1 ...
Страница 55: ...54 2008 Product Data 6 Wiring diagrams Outdoor units Models AS W2463 H3 Models AS W2468 H1 AS W2465DH2 ...