Dimensions
H
L6
L1
L7
W1
W1
W2
L8
D
80
160
L4
L5
L3
L2
D
Front side
250mm or more
900mm or more
250mm
or more
250mm
or more
76, Seongsan-dong, Changwon City
, Gyeongnam,
641-713, Korea
www
.lge.com/airconditioner
CHASSIS CODE: UW
, UY
Outdoor Unit
<Heat Pump>
ARUN340L
T2
ARUN360L
T2
ARUN380L
T2
<Cooling Only>
ARUV340L
T2(E)
ARUV360L
T2(E)
ARUV380L
T2(E)
W1 mm(inch)
1280(50.4)
W2 mm(inch)
806(31.5)
H mm(inch)
1607(63.3)
D mm(inch)
730(28.7)
L1 mm(inch)
1427(56.1)
L2 mm(inch)
692(27.2)
L3 mm(inch)
670(26.3)
L4 mm(inch)
900(35.4)
L5 mm(inch)
500(19.7)
L6 mm(inch)
704(27.7)
L7 mm(inch)
99(3.9)
L8 mm(inch)
82(3.2)
Notes:
1. Height of walls in case of pattern1:
Front side:1500mm, Suction side:500mm
2. If the above wall heights are exceeded, then h1/2 and h2/2 should be added to the
front and suction side service spaces respectively as shown in the following figure.
3. When installing the units, the most appropriate pattern should be selected from
those shown.
In order to obtain the best fit in the space available, always bear in mind the need
to leave enough room for a person to pass between units and wall and for the air to
circulate freely
. Y
our layout should take into account the possibility of short circuits.
4.
The Units should be installed to leave suf
ficient space in front for the on site
refrigerant piping work to be carried out comfortably
.
1500mm
500mm
h2
h1
Front side
Suction side