Service Manual 69
Troubleshooting Guide
The phenomena in case of connecting error
INDOOR UNIT
Connector Type
Condition
Open and connecting error
Open
Open
Open
Open
Short between terminals
(
and
) of ROOM-TH.
Short between terminals
(
and
) of PIPE-TH.
Short between terminals
• The same as the phenomenon of Outdoor Unit.
• The up/down vane does not operate.
• The up/down vane does not smoothly operate.
• It does not operate with a remote controller.
• The operation indicator blinks once
(on for 0.5 second, off for 3 seconds).
• The compressor operates continuously regardless
of the setting temperature and the variation of room
temperature.
• The operation indicator blinks once
(on for 0.5 second, off for 3 seconds)
• Continuous operation
• The operation indicator blinks once.
• The compressor and the outdoor fan stop.
• The indoor fan speed is low.
• The indoor fan does not operate.
• The operation indicator of Indoor unit blinks 8 times.
CN-DC/DC
CN-MOTOR
CN-UP/DOWN
CN-DISP
CN-TH
Blue
Black
Brown
Red
Phenomena
On for 0.5 second
Off for 3 seconds
Содержание ARTCOOL LAN091HNP
Страница 47: ...Service Manual 47 Schematic Diagram Schematic Diagram Heat Pump Cooling Only Series Indoor Unit ...
Страница 48: ...48 Room Air Conditioner Schematic Diagram Heat Pump Series Cooling Only Series Outdoor Unit ...
Страница 51: ...Service Manual 51 Schematic Diagram DISPLAY P W B ASM P No 6871A20921A PCB ASSEMBLY ...
Страница 52: ...52 Room Air Conditioner Schematic Diagram Wiring Diagram 1 Indoor Unit Cooling Only Models Heating Models ...
Страница 53: ...Service Manual 53 Schematic Diagram 2 Outdoor Unit Cooling Only Models Heating Models ...
Страница 76: ...P No 3828A20926C December 2006 Printed in Korea ...