Installation Manual 23
ENGLISH
Installation
Connection method of the connecting cable(Example)
1. Dismount two-caps on the conduit panel.
2. Make a hole appropriate for the passage of connection
cable through on cap by tool. (for low voltage line)
3. Pass the connecting cable through the hole.
4. Properly connect the cable on the terminal block.
5. Fix the connection cable with clamp cord provided on the
unit not to have strain at the terminal when the connection
cable is pulled outside up to a 35 pound weight.
6. Wind the vinyl tape round the connecting cable for sealing
between the surface of the connection cable and cap.
7. Mount the taped part of cable on the cap.
8. Finally, mount the holed cap with the
wound cable on the conduit panel.
WARNING:
Loose wiring may cause the terminal to overheat or
result in unit malfunction. A fire hazard may also exist.
Therefore, be sure all wiring is tightly connected.
When connecting each power wire to the corresponding
terminal, follow instructions "How to connect wiring to the
terminals" and fasten the wire tightly with the fixing screw
of the terminal plate.
How to connect wiring to the terminals
• For solid core wiring (or F-cable)
1. Cut the wire end with a wire cutter of wire-cutting
pliers, then strip the insulation to expose the solid wire
about 25mm(15/16")
2. Using a screwdriver, remove the terminal screw(s) on
the terminal plate.
3. Using pliers, bend the solid wire to from a loop suitable
for the terminal screw.
4. Shape the loop wire properly, place it on the terminal
plater and tighten securely with the terminal screw
using a screwdriver.
• For strand wiring
1. Cut the wire end with a wire cutter or wire-cutting
pliers, then strip the insulation to expose the strand
wiring about 10mm(3/8").
2. Using a screwdriver, remove the terminal screw(s) on
the terminal plate.
3. Using a round terminal fastener or pliers, securely
clamp each stripped wire end with a round terminal.
4. Position the round terminal wire, and replace and
tighten the terminal screw using a screwdriver.
G
Terminal
block
Cap
(Remove)
Clamp cord
Lock nut
Conduit panel
Cap(Reuse)
Taping
(for sealing)
Low voltage line
(connecting cable)
Power supply line
(1ø, 115V, 208/230V)
Hole (for low
voltage line)
Loop
Round
terminal
Insulation
Str
ip 25mm(15/16")
Str
ip 10mm(3/8")
Solid wire
Strand wire
Screw with
special washer
Screw with
special washer
Round terminal
Terminal plate
Wire
Wire
Round terminal