14 Room Air Conditioner
Installation
Piping Length and Elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
If piping length is more than 16.4ft(5m)
CAUTION: Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
Oil trap should be installed every 16.4~23feets (5~7 meters).
Pipe Size
Capacity
(Btu/h)
Suction
Evap
Max.
length
A
m(ft)
Additional
Refrigerant
g/m(oz/ft)
Max.
Elevation
B
m(ft)
Standard
Length
m(ft)
9k, 12k
Ø12.7mm(1/2") Ø6.35mm(1/4")
7.5(25)
7.5(25)
15(49)
20(0.22)
Содержание ARTCOOL LA091CNP
Страница 34: ...34 Room Air Conditioner Memo ...
Страница 35: ...P No 3828A22231B ...