48 | APPLICATION GUIDELINES
Single Zone W
all Mounted
Art Cool
™
Premier Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
EQUIPMENT SELECTION PROCEDURE
Cooling/Heating Correction Factors
For Single Zone Art Cool Premier systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, de-
termine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correction
factors as shown in the table below. Multiply the correction factors by the cooling or heating capacity obtained from the capacity tables using
design conditions. The resultant is the NET cooling or heating capacity.
Table 27:
Single Zone Wall Mounted Art Cool Premier Cooling/Heating % Coefficient Factors.
Model
Main Piping Length
Indoor Unit
Outdoor Unit
Feet
24.6
32.8
49.2
65.6
82
98.4
114.8
131.2
147.6
164
LAN090HYV1
LAU090HYV1
Cooling
100
98
93
88
-
-
-
-
-
-
Heating
100
99
96
94
-
-
-
-
-
-
LAN120HYV1
LAU120HYV1
Cooling
100
98
93
88
-
-
-
-
-
-
Heating
100
99
96
94
-
-
-
-
-
-
LAN150HYV2
LAU150HYV2
Cooling
100
100
100
100
100
100
-
-
-
-
Heating
100
98
95
91
88
84
-
-
-
-
LAN180HYV2
LAU180HYV2
Cooling
100
100
100
100
100
100
-
-
-
-
Heating
100
98
95
91
88
84
-
-
-
-
LAN180HYV1
LAU180HVY1
Cooling
100
100
100
100
100
100
-
-
-
-
Heating
100
98
95
91
88
84
-
-
-
-
LAN240HYV1
LAU240HVY1
Cooling
100
100
100
100
100
100
-
-
-
-
Heating
100
98
95
91
88
84
-
-
-
-