36 | PERFORMANCE DATA
Single Zone W
all Mounted
Art Cool
™
Premier Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
PERFORMANCE DATA
Maximum Heating Capacity
LA090HYV1, LA120HYV1
Outdoor Air
Temp.
Indoor Air Temperature (°F DB/ °F WB)
°F DB °F WB
60
64
68
70
72
75
86
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
-12
-13
7.79
1.01
7.83
1.02
7.86
1.03
7.92
1.05
7.78
1.04
7.59
1.04
6.99
1.05
-3
-4
9.82
1.06
9.76
1.06
9.71
1.06
9.69
1.06
9.62
1.08
9.47
1.10
9.02
1.17
0
-1
10.37
1.07
10.29
1.08
10.23
1.08
10.19
1.09
10.11
1.10
9.94
1.12
9.44
1.20
1
0
10.60
1.07
10.51
1.08
10.44
1.09
10.40
1.10
10.32
1.11
10.13
1.12
9.57
1.17
6
5
11.48
1.11
11.36
1.12
11.27
1.13
11.22
1.14
11.10
1.13
10.85
1.12
9.68
1.08
10
9
11.87
1.12
11.74
1.13
11.63
1.15
11.57
1.15
11.42
1.14
11.09
1.13
9.68
1.07
16
14
12.12
1.12
11.98
1.14
11.86
1.15
11.80
1.16
11.60
1.15
11.16
1.12
9.84
1.04
17
15
12.21
1.12
12.06
1.14
11.95
1.16
11.88
1.16
11.67
1.15
11.21
1.12
9.81
1.02
19
17
12.26
1.13
12.12
1.14
12.00
1.15
11.94
1.16
11.71
1.14
11.19
1.10
9.65
0.97
24
23
13.83
1.26
13.67
1.26
13.53
1.26
13.46
1.26
13.13
1.24
12.40
1.19
10.19
1.03
32
30
16.33
1.44
16.14
1.44
15.98
1.44
15.90
1.45
15.42
1.40
14.33
1.34
11.08
1.11
41
38
19.14
1.58
18.92
1.61
18.74
1.64
18.64
1.66
18.02
1.59
16.62
1.49
12.40
1.13
43
40
19.77
1.63
19.54
1.66
19.36
1.69
19.25
1.71
18.58
1.63
17.07
1.53
12.54
1.12
47
43
21.03
1.75
20.78
1.80
20.58
1.86
20.47
1.89
19.72
1.80
18.02
1.66
12.92
1.17
53
50
21.58
1.78
21.31
1.83
21.09
1.89
20.97
1.91
20.14
1.81
18.28
1.65
12.70
1.08
59
53
21.85
1.74
21.83
1.81
21.81
1.87
21.81
1.91
20.91
1.80
18.89
1.65
12.82
1.09
64
57
22.02
1.70
21.70
1.73
21.43
1.76
21.28
1.77
20.42
1.68
18.49
1.55
12.69
1.06
70
61
22.10
1.63
21.72
1.63
21.40
1.62
21.23
1.62
20.38
1.54
18.47
1.42
12.74
0.98
75
65
22.04
1.49
21.60
1.53
21.23
1.57
21.03
1.59
20.17
1.50
18.22
1.38
12.38
0.91
Table 21: LAN090HYV1/LAU090HYV1 Maximum Heating Capacities.
Outdoor Air
Temp.
Indoor Air Temperature (°F DB/ °F WB)
°F DB °F WB
60
64
68
70
72
75
86
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
-12
-13
9.42
1.28
9.47
1.29
9.50
1.30
9.52
1.31
9.42
1.31
9.18
1.31
8.46
1.32
-3
-4
11.87
1.34
11.81
1.34
11.75
1.34
11.72
1.34
11.64
1.36
11.45
1.39
10.91
1.48
0
-1
12.54
1.35
12.45
1.36
12.37
1.37
12.32
1.37
12.23
1.39
12.03
1.42
11.41
1.51
1
0
12.82
1.35
12.72
1.37
12.63
1.38
12.58
1.39
12.48
1.40
12.25
1.42
11.57
1.48
6
5
13.95
1.41
13.81
1.42
13.69
1.44
13.72
1.47
13.49
1.44
13.18
1.42
11.77
1.37
10
9
14.47
1.43
14.31
1.45
14.18
1.46
14.11
1.47
13.93
1.46
13.52
1.44
11.81
1.37
16
14
14.84
1.45
14.67
1.47
14.53
1.49
14.45
1.50
14.21
1.48
13.67
1.45
12.05
1.34
17
15
14.96
1.45
14.79
1.47
14.64
1.49
14.56
1.50
14.31
1.48
13.74
1.45
12.02
1.32
19
17
15.05
1.46
14.88
1.48
14.73
1.49
14.65
1.50
14.37
1.47
13.74
1.42
11.85
1.26
24
23
16.44
1.56
16.24
1.56
16.08
1.57
15.99
1.57
15.61
1.53
14.73
1.48
12.10
1.28
32
30
18.64
1.68
18.42
1.68
18.24
1.69
18.15
1.69
17.59
1.64
16.36
1.57
12.64
1.30
41
38
21.12
1.74
20.87
1.78
20.68
1.81
20.56
1.83
19.88
1.75
18.33
1.64
13.68
1.25
43
40
21.67
1.77
21.42
1.81
21.22
1.84
21.10
1.86
20.37
1.78
18.71
1.66
13.74
1.22
47
43
22.78
1.83
22.52
1.89
22.30
1.95
22.18
1.98
21.36
1.89
19.52
1.74
14.00
1.22
53
50
23.37
1.86
23.08
1.92
22.85
1.98
22.72
2.00
21.82
1.90
19.80
1.73
13.76
1.13
59
53
23.67
1.83
23.65
1.90
23.63
1.96
23.62
2.00
22.65
1.89
20.46
1.73
13.89
1.14
64
57
23.86
1.79
23.51
1.81
23.22
1.84
23.06
1.86
22.13
1.76
20.03
1.62
13.75
1.11
70
61
23.94
1.71
23.52
1.70
23.19
1.70
23.00
1.70
22.08
1.62
20.01
1.49
13.81
1.03
75
65
23.88
1.56
23.40
1.60
23.00
1.64
22.78
1.66
21.85
1.58
19.74
1.44
13.41
0.96
Table 22: LAN120HYV1/LAU120HYV1 Maximum Heating Capacities.
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor,indoor fan motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible. Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).