Installation Manual
25
How to Set E.S.P?
ENGLISH
ARNU48GBRZ4
2. Air flow rate
ARNU76GB8Z4, ARNU96GB8Z4
NOTE)
- Setting Value : ESP value
- The above table shows the correlation between the air rates and E.S.P.
Setting
Value
ESP (mmAq)
5
6
8
10
12
14
15
16
17
18
20
70
15.8
-
-
-
-
-
-
-
-
-
-
75
18.7
16
-
-
-
-
-
-
-
-
-
80
22.2
19.9
13.6
-
-
-
-
-
-
-
-
85
24.2
23.4
17.8
-
-
-
-
-
-
-
-
87
25.2
24.1
19.6
-
-
-
-
-
-
-
-
90
26.8
25.5
21.9
15.9
-
-
-
-
-
-
-
92
28.1
27
22.8
18.2
10.6
-
-
-
-
-
-
94
29
27
24
19.8
13.8
-
-
-
-
-
-
96
30.3
28.5
25
22.5
15.8
-
-
-
-
-
-
98
-
29.8
26.5
22.8
17.4
10.7
-
-
-
-
-
101
-
31.8
28
24.2
20.5
16
-
-
-
-
-
103
-
32.7
29.17
25.9
22
16.5
11.8
-
-
-
-
106
-
-
30.9
28.2
24.6
19.9
15.2
11.9
-
-
-
111
-
-
-
30.8
28.3
24.2
20.7
17.7
15.8
14.7
116
-
-
-
-
30.7
27.6
25.2
24.2
22.4
18.8
13.4
121
-
-
-
-
-
30.4
29.7
27.2
26.3
25.6
18.7
126
-
-
-
-
-
-
-
28.6
27.6
27.4
25.9
130
-
-
-
-
-
-
-
-
-
26.5
Setting
Value
ESP (mmAq)
6
9
12
15
18
20
22
23
25
55
25.39
-
-
-
-
-
-
-
-
60
33.65
-
-
-
-
-
-
-
-
65
40.01
30.29
-
-
-
-
-
-
-
70
46.43
35.81
17.31
-
-
-
-
-
-
75
50.93
45.35
35.57
-
-
-
-
-
-
80
55.77
51.91
42.86
26.57
-
-
-
-
-
85
-
54.22
49.74
42.67
20.9
-
-
-
-
88
-
-
52.72
46.44
33.72
-
-
-
-
90
-
-
52.54
48.82
40.09
23.07
-
-
-
92
-
-
-
50.91
44.3
23.46
-
-
-
94
-
-
-
50.9
46.73
39.65
13.87
-
-
96
-
-
-
-
49.84
44.04
24.17
23.63
-
98
-
-
-
-
49.66
48.09
39.72
25.28
14.49
100
-
-
-
-
-
48.23
42.56
40.34
15.47
102
-
-
-
-
-
-
46.41
45.92
38.6
105
-
-
-
-
-
-
-
46.51
45.44