Installation
10
Indoor Unit
n
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and duct
to absorb unnecessary vibration.
• Install the unit leaning to a drainage hole side
as a figure for easy water drainage.
• A place where the unit will be leveled and that
can support the weight of the unit.
• A place where the unit can withstand its
vibration.
• A place where service can be easily performed.
POSITION OF SUSPENSION BOLT
Drainage hole
M10 Nut
M10 washer
X 4
X 4
M10 Nut
M10 washer
X 4
X 8
A
B
C
D
(G)
H
I
E
F
B8 Chassis
BR Chassis
• Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable
amount of oil steam and flour adhere to the fan, the fin of
the heat exchanger, resulting in heat exchange reduction,
spraying, dispersing of water drops, etc.
In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting
hood on a cooking table has sufficient capacity so that it
draws oily steam which should not flow into the suction
of the air conditioner.
• Make enough distance from a cooking room to install
the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in
suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
NOTICE
Ceiling dimension and hanging bolt location
(Unit:mm)
A B C D E F G H I J K L
B8 1680 1565 1160 330 460 580 700 1400 1635 390 445 15
Dimension
Chassis
(Unit:mm)
A B C D E F (G) H I
BR 1282 1230 477 56 590 30 120 1006 294
Dimension
Chassis