Installation
8
Indoor Unit
4. The Control System
5. Wired Remote Controller
The products will only be controlled with the supplied wired remote controller. Other wired remote
controller will not be using the correct product.
6. Cycle check and SVC
For Outside Air Unit cycle check and SVC, LG MV 5.8 or later version should be used.
1) In case of connecting with Standard indoor units, Standard indoor unit should be a master unit.
Separate Outside Air Unit with Standard indoor units
Set only one of Standard indoor units to Master,
2) In case of using central remote controller, mixture of indoor units and Outside Air Unit in
same zone is not possible.
Separate Outside Air Unit zone with Standard indoor units zone.
OAU
48 kBtu/h
ZONE 1
OAU
48 kBtu/h
48 kBtu/h
48 kBtu/h
Standard
Standard
ZONE 2
OAU
48 kBtu/h
ZONE 1
OAU
48 kBtu/h
48 kBtu/h
48 kBtu/h
Standard
Standard
ZONE 2
OAU
Set one of the Standard Indoor Unit to Master
Standard
Standard
Standard
Slave
* OAU : Outside Air Unit
Standard: Standard Indoor Unit