Installation Manual
11
ENGLISH
Installation
1. Remove the Air Filter.
2. Check the drainage.
• Spray one or two glasses of water upon the
evaporator.
• Ensure that water flows drain hose of indoor
unit without any leakage.
Checking the Drainage
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
■
After all workings are finished, check the working and operation.
• Air distribution ............... Is the air circulation good?
• Drain ............................. Is the drainage smoothly and no sweating?
• Gas leakage ................. Is the piping connection correctly?
• Wiring ........................... Is the wiring connection correctly?
• Lock-bolt ....................... Is the lock-bolt of compressor loosened?
• Insulation
Is the unit fully insulated?
• Ground
Is the unit safely grounded?
THERMAL INSULATION
TEST AND CHECK
Make sure that there is no clearance here.
Overlap with thermal
insulator for piping.
Thermal insulator for refrigerant pipe
(Local supply)
Thermal insulator for
piping(Local supply)
Hose clip for thermal insulator(Local supply)
Union for gas pipe
Refrigerant pipe and thermal
insulator(Local supply)
Union for liquid pipe
Thermal insulator for refrigerant pipe
(Local supply)
Hose clip for thermal insulator
(Local supply)
Felt
Rubber
Insulation
No clearance
Cabinet
.......................
.........................
Содержание ARNU12GB1G2
Страница 20: ...20 Indoor Unit 20 Indoor Unit 20 Indoor Unit Memo ...
Страница 40: ...20 Unità interna 20 Unità interna Note ...
Страница 60: ...20 Unidad interior 20 Unidad interior Nota ...
Страница 80: ...20 Unité intérieure 20 Unité intérieure Note ...
Страница 100: ...P No MFL After reading this manual keep it in a place easily accessible to the user for future reference 51834805 ...