How to Set E.S.P?
18
Indoor Unit
How to Set E.S.P?
Setting Value
Static Pressure(mmAq(Pa))
0 (0)
1 (10)
2 (20)
3 (29)
4 (39)
5 (49)
60
-
-
-
-
-
-
65
5.03
-
-
-
-
-
70
5.60
4.85
-
-
-
-
75
6.19
5.44
4.57
-
-
-
80
6.79
6.05
5.17
-
-
-
85
7.41
6.67
5.80
4.80
-
-
90
8.05
7.31
6.43
5.44
-
-
95
8.71
7.96
7.09
6.09
4.97
-
100
9.38
8.63
7.76
6.76
5.64
-
105
10.07
9.32
8.45
7.45
6.33
5.08
110
-
10.03
9.16
8.16
7.04
5.79
115
-
-
9.88
8.88
7.76
6.51
120
-
-
-
9.62
8.50
7.25
125
-
-
-
10.38
9.26
8.01
130
-
-
-
-
10.03
8.78
ARNU05GL1G2, ARNU07GL1G2, ARNU09GL1G2
Setting Value
Static Pressure(mmAq(Pa))
0 (0)
1 (10)
2 (20)
3 (29)
4 (39)
5 (49)
75
6.50
-
-
-
-
-
80
7.34
6.70
-
-
-
-
85
8.20
7.55
6.69
-
-
-
90
9.07
8.43
7.56
6.47
-
-
95
9.96
9.32
8.45
7.36
-
-
100
10.87
10.22
9.36
8.27
6.96
-
105
11.79
11.15
10.28
9.19
7.89
6.35
110
12.73
12.09
11.22
10.14
8.83
7.30
115
13.69
13.05
12.18
11.09
9.78
8.25
120
14.67
14.02
13.16
12.07
10.76
9.23
125
15.66
15.01
14.15
13.06
11.75
10.22
130
16.67
16.02
15.16
14.07
12.76
11.23
135
-
-
16.18
15.10
13.79
12.26
140
-
-
-
16.14
14.83
13.30
145
-
-
-
-
15.89
14.36
ARNU12GL2G2, ARNU15GL2G2, ARNU18GL2G2
(Unit : CMM)
(Unit : CMM)
(Unit : CMM)
ARNU21GL3G2, ARNU24GL3G2
Setting Value
Static Pressure(mmAq(Pa))
0 (0)
1 (10)
2 (20)
3 (29)
4 (39)
5 (49)
85
10.19
-
-
-
-
-
90
12.18
10.71
11.09
-
-
-
95
13.81
12.34
12.19
-
-
-
100
15.16
13.69
13.38
10.71
-
-
105
16.30
14.83
14.36
11.85
-
-
110
17.31
15.85
15.23
12.86
10.97
-
115
18.27
16.80
16.07
13.82
11.93
-
120
19.26
17.79
16.93
14.80
12.91
10.49
125
20.34
18.87
17.89
15.88
13.99
11.57
130
21.60
20.13
19.01
17.14
15.25
12.83
135
-
21.64
20.36
18.66
16.76
14.35
140
-
-
22.01
20.50
18.61
16.19
145
-
-
-
22.75
20.86
18.44
Note :
1. The above table shows the correlation between the air rates and E.S.P.
2. Please refer wired remote controller manual for E.S.P setting procedure.