Space CO
2
Sensor
When a unit is designed with CO
2
control, CO
2
sensor is
needed to be supplied at field. LG DOAS includes a
CFM modulation controls sequence based on CO
2
value. The sensor must be mounted in the space at a
height of approximately five (5) feet from the floor.
Wiring between the Unit and the space CO
2
sensor must
be through a field-supplied, three-conductor, 18 AWG,
and stranded communication cable.
Terminations must be made per the following chart.
Sensor setting
LG recommend
- CO
2
Sensor (0~10Vdc):
Honeywell (C7232A1008
)
Table 13: Space CO
2
Sensor Termination @ Main Module
Space CO
2
Sensor
Type
0~10Vdc
Terminal Strip TB
@ Main Module
UI8
G
Figure 20: CO
2
sensor connection (0~10Vdc)
Differential Pressure Sensor (Exhaust)
When a unit is designed with Air Volume (CFM) Control
at exhaust fan. A differential pressure sensor is needed
to be supplied at field.
The sensor must be mounted at the location below.
Wiring between the Unit and the Differential Pressure
sensor must be through a field-supplied, three-
conductor, 18 AWG, and stranded communication cable.
Terminations must be made per the following chart
Note
:
LG recommend
- Differential Pressure Sensor (0~10Vdc):
Differential Pressure Sensor (for Exhaust)
Type
0~10Vdc
Terminal Strip TB
@ Main Module
UI6
G
Figure 21: Differential Pressure sensor Installation