INSTALLATION OF OUTDOOR UNIT
ENGLISH
Floor Standing Air conditioner
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
• Do not use the pipe less than 5 m. Otherwise, it may cause damage of compressor and to
form dewdrop on the indoor unit. Also, it may cause to decrease capacity.
• Capacity is based on the length of 5 m and maximum allowance length is on the basis of
reliability.
• Improper refrigerant charge may result in abnormal cycle.
CAUTION
!
If installed tube is shorter than 5 m, additional charging is not necessary.
Additional Refrigerant = (A -5) x Additional refrigerant (g)
Piping length and the elevation
MODEL
Pipe Size
Length A (m)
Elevation B (m)
Additional Refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
APUQ55GT3E0
APUQ55GT3M0
Ø19.05(3/4) Ø 9.52(3/8)
5
30
-
20
30
APUQ55LT3E0
APUQ55LT3M0
APUQ55GT3A0
APUQ50LT3E0
APUW55GT3E0
APUW55GT3M0
APUW55LT3E0
APUW55LT3M0
APUW50GT3E0
APUW50LT3E0
Ø19.05(3/4) Ø 9.52(3/8)
5
30
-
20
40