10
WIRING CONNECTION
ENGLISH
<Outdoor Unit Power Supply : 1 Ph>
Indoor unit
Outdoor unit
POWER SUPPLY
1(L) 2(N) 3
1(L) 2(N) 3
)
N
(
2
)
L
(
1
<Outdoor Unit Power Supply : 3 Ph>
Indoor unit
Outdoor unit
POWER SUPPLY
1(L) 2(N) 3
1(L) 2(N) 3
The power cord connected to the outdoor unit should be complied withIEC 60245 or HD 22.4
S4 (This equipment shall be provided with a cord set complying with the national regulation.
The connecting cable connected to the outdoor unit should be complied with IEC 60245 or
HD 22.4 S4 (This equipment shall be provided with a cord set complying with the national
regulation.)
If the supply cord is damaged, it must be replaced by a special cord or assembly availible
from the manufacturer of its service agent.
When the connection line between the in-
door unit and outdooor unit is over
40(131.2) m(ft), connect the telecommuni-
cation line and power line separately.
CAUTION
!
GN/
YL
20mm
20mm
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
20(25/
32) mm
(inch)
GN
/YL
35(1
-3/8
) ±
5(3/1
6) mm(inch
)
10(13/32) ± 3(1/8) mm(inch)
Model
Phase(Ø) Area(mm
2
)
ATUQ18GPLE6
1
2.5 (12AWG)
ATUQ24GPLE6/APUQ24GS1A3
1
4.0 (10AWG)
APUQ30GR5A3
1
4.0 (10AWG)
ATUQ30LNLE6
3
2.5 (12AWG)
ATUQ36GNLE6/APUQ36GR5A3
1
4.0 (10AWG)
ATUQ36LNLE6/APUQ36LR5A3
3
2.5 (12AWG)
ATUQ48GMLE6/APUQ48GT3E3
1
6.0 (6AWG)
ATUQ48LMLE6/APUQ48LT3E3
3
2.5 (12AWG)
Connecting Cables between Indoor Unit and Outdoor Unit
1,MFL67448529,영영 2017. 6. 19. 영영 3:45 Page 10