Selection of the best location
- Where optimum air distribution can be ensured.
- Where nothing blocks air passage and install the duct work.
- Where condensate can be properly drained.
- Where the ceiling is strong enough to bear the indoor unit weight.
- Where the false ceiling is not noticeably on an incline.
- Where sufficient clearance for maintenance and service can be ensured.
- Where piping between indoor and outdoor units is possible within the allowable limit. Refer to
the installation manual for the outdoor unit.
More than
250(9-27/32)
More than
250(9-27/32)
Unit: mm (inch)
More than
350(13-25/32)
More than
350(11-25/32)
More than
600(23-5/8)
clearance from
access panels
for Service
NOTE
!
• The remote control may operate other electronic devices if pointed towards them. Make
sure to point the remote control towards the signal receiver of the air conditioner.
• For proper operation, use a soft cloth to clean the signal transmitter and receiver.
CAUTION
In case that the unit is installed near the sea, the installation parts may be corroded by salt.
The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
!