30
Multi Air Conditioner
Flaring Work and Connection of Piping
Align the center of the piping and sufficiently
tighten the flare nut by hand.
Connecting pipe order
1) ROOM A~C gas side pipe
2) ROOM A~C liquid side pipe
Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque
wrench ensure the direction for tightening fol-
lows the arrow on the wrench.
Ø12.7(1/2 inch)
Connector
Outdoor unit
Liquid
side piping
Main liguid
side valve
Main gas
side valve
ROOM A
ROOM B
ROOM C
Gas side
piping
Connection of piping - Outdoor
Outside diameter
Torque
mm
inch
N. m
kgf.m
lbf.ft
Ø6.35
1/4
14~18
1.4~1.8
10~13
Ø9.52
3/8
34~42
3.5~4.3
25~31
Ø12.7
1/2
49~61
5.0~6.2
36~45
Ø15.88
5/8
69~82
7.0~8.4
51~60
Ø19.05
3/4
100~120 10.0~12.2
73~88