Installation Manual
21
ENGLISH
Installation
14.12 Condensed water piping connection
• Install the drain pipe to be as short as possible and the inclination should be at a minimum of 1/100.
• For the size of the drain pipe, use the same size as the air condition connecting pipe or wider.
• For the drain pipe and connecting socket, you must cover them with lagging material so that icing
is not formed. Lagging material thickness: 2"(50mm)
• By using the drain trap as shown in the following diagram, make sure the drain pressure reduction
is not applied.
• Make sure you do not mistakenly mix the condensed water outlet and the coolant outlet. It can cause a
problem or an accident.
• When connecting the condensed water pipe, always wrap Teflon tape on the screwed part. If not, it can
cause a leakage to cause an accident.
CAUTION
2"(50mm)
Condensed water pipe
Machine room
condensed water pipe