32
INSTALLATION OF UNIT
ENGLISH
Display
Title
Cause of Error
Outdoor unit related error
7
5
1
Master Fan CT Sensor Error
Master Fan CT Sensor open or short
2
Slave Fan CT Sensor Error (For
20/23/25RT Only)
Slave Fan CT Sensor open or short
7
6
1
Master Fan DC Link High Voltage Error
Master Fan Current is abnormal
2
Slave Fan DC Link High Voltage Error
(For 20/23/25RT Only)
Slave Fan Current is abnormal
7
7
1
Master Fan Over Current Error
Master Fan Current is over 10A
2
Slave Fan Over Current Error (For
20/23/25RT Only)
Slave Fan Current is over 10A
7
9
1
Master Fan Start Failure Error
Master Fan First Position Sensing Failure
2
Slave Fan Start Failure Error (For
20/23/25RT Only)
Slave Fan First Position Sensing Failure
8
6
1
Master Main PCB EEPROM Error
Communication Fail between Master Main MICOM and
EEPROM or omitting EEPROM
2
Slave Main PCB EEPROM Error (For
20/23/25RT Only)
Communication Fail between Slave Main MICOM and
EEPROM or omitting EEPROM
8
7
1
Master Fan PCB EEPROM Error
Communication Fail Between Master Fan MICOM and
EEPROM or omitting EEPROM
2
Slave Fan PCB EEPROM Error (For
20/23/25RT Only)
Communication Fail Between Slave Fan MICOM and
EEPROM or omitting EEPROM
1,MFL67445803,영영 2018. 2. 19. 영영 5:00 Page 32