INSTALLATION OF UNIT
3
1
ENGLISH
Function
Description
Setting "Off"
Setting "On"
Default
SW3
Group Control
Selection of Master or
Slave
Master
Slave
Off
SW4
Dry Contact Mode
Selection of Dry Contact
Mode
Variable
Auto
Off
SW5
Return Air Sensor
Installed Sensor or Not
Not installed
Installed
Off
SW6
CTI
Installed CTI or not
Not installed
Installed
Off
* Default setting of all Dip S/W is off.
Group Control
It operates maximum 16 Units by only one Wired Remote Controller,
and each Unit starts sequentially to prevent over current.
- Using the supplied Wired Remote Controller, wire them like above.
- Ensure that the color of wire.
- If the main PCB is not directly connected to the wired remote controller, set the Dip switch “3"
in the main PCB as "ON" position.(OFF ’ Master / ON ’ Slave)
- Please connect with same type unit. (Single Package)
- If there were connected with different type Indoor unit, It is can not operate some functions.
Indoor Unit 1
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Main PCB
#1
Main PCB
#2
Main PCB
#16
Wired Remote Controller
Indoor Unit 2
Main PCB
Indoor Unit 16
Connector
RED(12V)
YL(SIGNAL)
BK(GND)
RED(12V)
YL(SIGNAL)
BK(GND)
YL(SIGNAL)
BK(GND)
Connecting Cable(Local Supply)
Connector
Connector
....
....
YL(SIGNAL)
BK(GND)
YL(SIGNAL)
BK(GND)
YL(SIGNAL)
BK(GND)
DIP Switch
Indoor PCB
Dip Switch Setting in Indoor Main PCB