INSTALLATION OF THERMOSTAT
29
ENGLISH
Test Equipment
Turn on power to the system
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
1) Press the fan button to select the On position. The blower should begin to operate.
2) Press the fan button to select the Auto position. The blower should stop immediately.
Heating System
1) Press the System button to select the Heat position. Heat Pumps only - if the auxiliary heating
system has a standing pilot, be sure to light it.
2) Press to adjust thermostat setting to 1° above room temperature. The heating system should
begin to operate and the thermostat will indicate Heat On.
3) For heat pumps with auxiliary- Press to adjust thermostat setting to 3° above room
temperature.
The auxiliary heat should begin to operate and the thermostat will indicate Heat On Aux.
4) Press to adjust thermostat setting 1° below room temperature. The heating system should
stop operating and the Heat On icon will disappear.
Auxiliary System (only for heat pumps with auxiliary)
1) Press the system button to select the Aux position. This bypasses the heat pump and runs
auxiliary only heat.
2) Press to adjust thermostat setting to 1° above room temperature. The auxiliary heating system
should begin to operate and the thermostat will indicate Heat On Aux.
3) Press to adjust thermostat setting 1° below room temperature. The auxiliary heating system
should stop operating and the Heat On Aux icon will disappear.
Cooling System
1) Press the system button to select the Cool position.
2) Press to adjust thermostat setting 1° below room temperature. The blower should come on
immediately on high speed, followed by cold air circulation. The thermostat will indicate Cool
On. There can be up to a 5 minute delay. (see INSTALLER MENU, item 50)
3) Press to adjust thermostat setting to 1° above room temperature. The cooling system should
stop operating and the Cool On icon will disappear.
NOTE
If Starting Soon is shown on the display, the compressor lockout feature is operating. There will
be up to a 5 minute delay before the compressor turns on (see INSTALLER MENU, item 50).
Installer Menu #
(Hold Menu 8
Seconds)
Description
Default Setting
(flashing icons)
Settings (Press
▲
or
▼
)
88
Auto Changeover: thermostat
automatically switches
between heat and cool.
OFF
On – enable auto
OFF – disable auto
99
Keypad Lock: prevent
unwanted changes to the
thermostat
OFF
On – disable buttons
OFF – all buttons are active