Pipe thermistors Installation
Location of the pipe thermistors
A correct installation of the thermistors is
required to ensure a good operation :
1
Pipe_In
: Install the thermistor behind the
distributor on the coldest pass the heat
exchanger
(contact your heat exchanger dealer).
2
Pipe_Out
: Install the thermistor at the outlet of the
heat exchanger as close as possible to
the heat exchanger.
Evaluation must be done to check if the
evaporator is protected against freeze-up.
Execute test operation and check for freeze-
up.
1
Ø6.3
Ø8.2
2
(AHU)
THERMISTORS INSTALLATION
ENGLISH
THERMISTORS INSTALLATION
22
INSTRUCTION
• To prevent condensation from
accumulating on the bottom of the pipe
sensor, install the sensor by lifting it up
as shown below.
• In order to detect the temperature of
the pipe well, install the sensing part so
that it can be attached to the pipe well
as shown below
Wa
te
r
45°
Most sensitive
point of the
thermistor