- 84 -
Error code check
Error number
Errors
Meaning
Main cause of occurrence
67
(671)
Fan Lock Error
Fan RPM is 10 RPM or
less for 5 sec. when
ODU fan starts or 40
RPM or less after fan
starting.
1. Fan motor defect / assembly condition abnormal
2. Wrong connection of fan motor connector
3. Reversing rotation after RPM target apply
4. Fan PCB assembly defect
5. Fan lock by Heavy Snowfall.
n
Failure diagnosis method
Is ODU Fan Motor Assemble
condition normal?
No
Yes
Recheck power and installation condition
Check ODU Fan Motor assemble condition and fan locking
→
Reassemble or replace if abnormality found
Is ODU Fan Motor normal?
No
Yes
1. Check resistance between each phase(U,V,W) of fan
motor terminal
-Panasonic Motor : 9.5 Ω ± 5 % (@25 ℃)
-LG Motor : 8.6 Ω ± 7 % (@25 ℃)
2. Check insulation resistance between fan motor
terminal(U,V,W)
→
Replace fan motor if abnormality
found
Is wire connection of
ODU Fan Motor wire normal?
No
Yes
Check wiring between fan motor and fan PCB
→
Reassemble if abnormality found
Is Fan PCB assembly normal?
No
Yes
Replace Fan PCB assembly
* Fan Motor resistance measuring
between each phase
* Fan Motor Wire connection