- 49 -
The phenomena from main component failure
Failure code
Failure name
Occurrence condition
Control when occurring
Removal condition
CHxx042
Low pressure sensor error
Low pressure sensor is short/open
Stop applicable cycle
Automatically return to normal condition
CHxx043
High pressure sensor error
High pressure sensor is short/open
Stop applicable cycle
Automatically return to normal condition
CHxx045
Heat exchanger temperature sensor error
Heat exchanger temperature sensor is short/open
Stop applicable cycle
Automatically return to normal condition
CHxx046
Suction temperature sensor error
Suction temperature sensor is short/open
Stop applicable cycle
Automatically return to normal condition
CHxx050
Chiller 3 phase power missing phase
Chiller 3 phase power missing phase
Stop applicable cycle
Automatically return to normal condition
Содержание ACHH Series