14
CONNECTING PIPES
ENGLISH
Connecting the pipes to the
Outdoor unit
Align the center of the piping and sufficiently
tighten the flare nut by hand.
Finally, tighten the flare nut with torque
wrench until the wrench clicks.
- When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
h
When tighten the pipe, hold the haxagonal
body.
When connecting in a downward direction,
knock out the knock-out hole of the base pan.
(refer to figure 2)
Preventing foreign objects from entering
(Figure3)
- Plug the pipe through-holes with putty or
insulation material(procured locally)to stop up
all gaps,as shown in the figure 3.
Outside diameter
Torque
mm
inch
N·m
Ø 6.35
1 / 4
16±2
Ø 9.52
3 / 8
38±4
Ø 12.7
1 / 2
55±6
Ø 15.88
5 / 8
75±7
Ø 19.05
3 / 4
110±10
Sideways
Backward
<Figure 1>
Knock-out
Base pan
<Figure 2>
Gas side piping
Liquid side piping
Drain hose
Connecting wire
Connection pipe
<Figure 3>
Putty or insulating material
(produced locally)
Содержание ABUQ60LM3T1