FUNCTION
21
ENGLISH
Forced Cooling Operation
Adding the refrigerant in winter.
• When the green LED of PCB is on, com-
pressor is going to be off because of low
pressure.
• You should return the Dip Switch to oper-
ate normally after finishing the operation.
• Improper Pump down will lead to product
turn off along with LED (green &red) off
with in 20 minutes from the initial start.
Pump Down Dip S/W Setting
Power on
(Red LED On, Green LED Off)
WARNING
!
Setting Procedure
- Set the Dip Switch as follow after shutting the power source down.
- Reset the power.
- Red LED and Green LED of PCB lights during work. (The indoor unit is operated by force.)
- If operation is done, Red LED will be turned off.
If operation is not done normally, Red LED will blink.
- Close the Liquid valve only after green LED turned off (7 minutes from the start of the machine).
Then close the gas valve after Green LED on.
ABUQ18GM1T0
ABUQ24GM1T0
ABUQ30GM1T0
ABUQ36GM3T0
ABUQ48LM3T0
ABUQ54LM3T0
Liquid Valve
Closed
Gas Valve
Closed
Comp on
(Red LED On, Green LED On)
Pump Down Start
(Red LED On, Green LED Off)
Pump Down Complete
(Red LED Off, Green LED On)
Power off
(Red LED Off, Green LED On)
FUNCTION
6
7
8