Installation of Indoor, Outdoor Unit
Installation Manual
9
ENGLISH
2. Outdoor unit
1. If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.
2. Ensure that the spaces indicated by arrows
around front, back and side of the unit.
3. Do not place animals and plants in the path
of the warm air.
4. Take the air conditioner weight into account
and select a place where noise and vibration
are minimum.
5. Select a place so that the warm air and noise
from the air conditioner do not disturb
neighbors.
More than
30cm
More than 30cm
More
than 60cm
More than 60cm
More than
70cm
3. Piping length and the elevation
Outdoor unit
Indoor unit
A trap is not necessary when the
outdoor unit is installed in a higher
position than the indoor unit.
CAUTION:
• Rated performance for refrigerant line length of:7.5m (ABUQ09GL1A0,
ABUQ12GL2A0)
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
MODEL
Pipe Size (Diameter:Ø)
Length A(m)
Elevation B(m)
*Additional
refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
ABUQ09GL1A0 3/8"(9.52mm) 1/4"(6.35mm)
7.5
15
5
10
20
ABUQ12GL2A0 3/8"(9.52mm) 1/4"(6.35mm)
7.5
15
5
10
20