ABNW36GM2E4
Egypt Models
[Table. 2]
Step CMM
Static Pressure[mmAq(Pa)]
2(20) 2.5(25) 3(29) 4(39) 6(59) 8(78) 10(98) 12(118) 13(127) 14(137) 15(147)
Setting Value
HIGH 16.5
85
87
90
94
103
110
118
125
128
131
134
MID
14.5
76
77
85
91
97
107
114
121
125
128
131
LOW
13
73
74
77
88
93
103
111
117
120
125
128
HIGH
18
90
92
95
99
108
115
122
129
132
135
138
MID
16.5
85
87
90
94
103
111
118
125
128
131
134
LOW
14.5
76
77
85
89
97
106
114
121
124
127
130
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
Model
ABNW24GM1E4
ABNW30GM1E4
Step
CMM
Static Pressure[mmAq(Pa)]
2(20) 2.5(25) 3(29)
4(39)
5(49)
6(59)
7(69)
8(78)
9(88)
10(98)
Setting Value
32 : 01 32 : 02 32 : 03 32 : 04 32 : 05 32 : 06 32 : 07 32 : 08 32 : 09 32 : 10
HIGH
32
88
90
96
100
104
108
112
116 119
MID
28
80
83
90
94
98
103
108
112 115
LOW
24
74
76
82
88
94
99
104
108 111
92
85
78
Model
NOTE
1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
Factory set (E.S.P.)
mmAq(Pa)
Lower Limit (E.S.P)
mmAq(Pa)
Upper Limit (E.S.P)
mmAq(Pa)
2(20)
2(20)
6(59)
15(147)
15(147)
6(59)
ABNW36GM2E4
Model
ABNW24GM1E4
ABNW30GM1E4
8(78)
2(20)
10(98)
!
NOTE
* If it is zero static pressure, please set value below Maximum value.
Maximum Value
98
115
115
ABNW36GM2E4
Model
ABNW24GM1E4
ABNW30GM1E4
30
INSTALLATION INSTRUCTION
ENGLISH