1
Pressing the
key and
key
simultaneously for more than 3 seconds can
enter the manual setting mode of the system.
- After entering the manual setting mode,
press the
key to select the code value for
central control address setting.
* The code value for central control address
setting is: 02
2
Set codes of the group and indoor unit through
the temperature up and down adjustment
buttons (
,
).
For example, set to
[Group code = 2 Indoor unit code = 3] The
content will be displayed as shown in the left
figure.
3
Press the
key to save the setting value
4
After the setting is completed, press the
key and
key simultaneously for more than
3 seconds to exit the address setting mode.
- If there is no key input within 25 seconds, the
system will also exit the manual setting mode
automatically.
Note
: If the central controller locks the wired controller, ‘HL’ is displayed on the latter.
* When the central controller is locked, the wired controller, which displays ‘HL’, cannot control
the indoor unit.
Group code
Indoor unit code
• If the indoor unit and the central control are connected, the central control address of the indoor
unit needs to be set so that the central controller can identify each indoor unit.
• The central control address consists of the group code and the indoor unit code.
Installer Setting - Central Control Address Setting
This function is used to connect to the central control. Please refer to the central controller
manual for details.
ENGLISH
19
INSTALLATION INSTRUCTION